420010312300 MULTICALOR 1500.1 - 1800.1 PR/PR TS
EN
ADJUSTMENT OF GAS MINIMUM PRESSURE SWITCH
Unscrew off and remove cover M. - Set regulator N to a value equal to 60% of gas nominal feed pressure
(i.e. for nat. gas nom. pressure = 20 mbar, set regulator to a value of 12 mbar; for L.P.G. nom.
pressure of G30/G31- 30/37 mbar, set regulator to a value of 18 mbar).Screw up cover M
ADJUSTMENT OF THE AIR PRESSURE SWITCH
Unscrew screws A and B and remove cover C.- Set the pressure switch to the minimum by
turning regulator D to position 1.
- Start the burner and keep in low flame running, while checking that combustion is cor-
rect. Through a small cardboard, progressively obstruct the air intake until to obtain a CO2 increase of
0,5÷0,8% or else, if a pressure gauge is available, connected to pressure port E, until reaching a
pressure drop of 1 mbar (10 mm of W.G.). - Slowly increase the adjustment value of the air
pressure switch until to have the burner lockout. Remove the obstruction from the air intake,
screw on the cover C and start the burner by pressing the control box rearm button.
Note: The pressure measured at pressure port E must be within the limits of the pressure
switch working range. If not, loose the locking nut of screw F and gradually turn the same:
clockwise to reduce the pressure; counterclockwise to increase. At the end tighten the locking nut.
UV CELL
Fotocellula
FIRING HEAD SETTING
DETECTOR CURRENT
Microamperometer
Microamperometro
full scale 1000 µA
LFL 1.333
LFL 1.622
fondo scala 1000 μA
min 70
μA
The detector current is checked by inserting a microamme-
LANDIS
ter (scale 1000 µA - d.c.) in series with the uv cell..
The flame detector current has to been > 70 µA.
22 23
22
-
+
N
M
I
L
D
C
A
G
B
H
E
F