3.3
Extracción de los accesorios de la
unidad exterior
5~12 HP
Compruebe que la unidad incorpora todos los accesorios.
a
b
1×
1×
REQUEST FOR THE INDICATION OF INSTALLATION INFORMATION
1. RECORD OF INDOOR UNIT MODEL AND INSTALLATION SITE
No.
1
2
3
4
MODELNAME
INSTALLATION
SITE
No.
11
12
13
14
INSTALLATION
MODELNAME
SITE
No.
21
22
23
24
MODELNAME
INSTALLATION
SITE
No.
31
32
33
34
INSTALLATION
MODELNAME
SITE
No.
41
42
43
44
INSTALLATION
MODELNAME
SITE
No.
51
52
53
54
MODELNAME
INSTALLATION
SITE
No.
61
62
63
64
MODELNAME
INSTALLATION
SITE
2. RECORD FOR SETTINGS (CONTENTS SEE INSTALLATION MANUAL)
SETTING
VALUE
REMARK
DATE
3. RECORD OF INSTALLATION DATE
DAY
MONTH
YEAR
6. AFTER EQUIPPING, PLEASE PUT IT ON THE BACK SIDE OF THE FRONT PLATE.
f
g
1×
1×
a
Precauciones generales de seguridad
b
Manual de instalación y de funcionamiento
c
Etiqueta de carga de refrigerante adicional
d
Pegatina de información sobre la instalación
e
Etiqueta de información relativa a gases fluorados de
efecto invernadero
f
Etiqueta multilingüe de información relativa a gases
fluorados de efecto invernadero
g
Bolsa de accesorios para tubería
3.4
Tubos accesorios: Diámetros
Tubos accesorios (mm)
Tubería de gas
▪ Conexión delantera
ID Øa
ID Øb
▪ Conexión inferior
ID Øa
OD Øb
Tubería de líquido
▪ Conexión delantera
ID Øb
ID Øa
▪ Conexión inferior
ID Øb
ID Øa
REYQ8~20+REMQ5U7Y1B
VRV IV+ recuperación de calor
4P561154-1 – 2018.09
14~20 HP
c
d
e
1×
1×
1×
REQUEST FOR THE INDICATION OF ADDITIONAL REFRIGERANT CHARGING AND LEAK DETECTION OPERATION RESULT
BE SURE TO FILL OUT THE BLANKS, WHICH ARE NEEDED FOR AFTER-SALE SERVICES.
BE SURE TO FILL OUT THE BLANKS, WHICH ARE NEEDED FOR AFTER-SALE SERVICES.
5
6
7
8
9
10
1. CALCULATION OF ADDITIONAL REFRIGERANT CHARGING AMOUNT
CALCULATE THE ADDITIONAL REFRIGERANT CHARGING AMOUNT BASED ON THE FORMULA BELOW BEFORE CHARGING.
WHEN RE-CHARGING TOTAL AMOUNT OF REFRIGERANT , CHARGE THE TOTAL OF THE AMOUNT CHARGED AT
SHIPMENT (INDICATED ON THE MACHINE NAMEPLATE) AND THE ADDITIONAL AMOUNT SHOWN AS FOLLOWS :
capacity connection
Total indoor unit
15
16
17
18
19
20
kg
ratio (CR)
8HP
10-12HP 14-16HP 18-20HP
OUTDOOR
ADDITIONAL CHARGING
TOTAL LENGTH OF LIQUID
TOTAL LENGTH OF LIQUID
TOTAL LENGTH OF LIQUID
Total indoor unit capacity
when piping length <30m
50%< CR < 105%
105%< CR < 130%
0.5
0
0.5
0
0.5
0
0.5
1.0
UNIT
AMOUNT
PIPE SIZE O22.2 x 0.37
PIPE SIZE O19.1 x 0.26
PIPE SIZE O15.9 x 0.18
Total indoor unit capacity
50%< CR < 70%
70%< CR < 85%
0.3
0
0.5
0
0.5
0
0.5
1.0
25
26
27
28
29
30
kg
(m) x 0.37
(m) x 0.26
(m) x 0.18
when piping length >30m
85%< CR < 105%
105%< CR < 130%
0.7
1.2
1
1.5
1.5
1
2.0
1.5
TOTAL LENGTH OF LIQUID
TOTAL LENGTH OF LIQUID
TOTAL LENGTH OF LIQUID
PIPE SIZE O12.7 x 0.12
PIPE SIZE O9.5 x 0.059
PIPE SIZE O6.4 x 0.022
ONLY FOR RYYQ8~20 MODELS
35
36
37
38
39
40
(m) x 0.12
(m) x 0.059
(m) x 0.022
kg
RYYQ8~12
0.9
RYYQ14-16
1.1
RYYQ18-20
1.3
2. RECORD OF ADDITIONAL REFRIGERANT CHARGE AMOUNT AND RESULT OF LEAK CHECK OPERATION
45
46
47
48
49
50
DATE
AMOUNT
55
56
57
58
59
60
RESULT LEAK CHECK
DATE
AMOUNT
RESULT LEAK CHECK
DATE
AMOUNT
RESULT LEAK CHECK
SETTING
VALUE
REMARK
DATE
DATE
AMOUNT
RESULT LEAK CHECK
3. FOR DETAILS CONCERNING PIPING SELECTION AND CALCULATION OR HOW TO OPERATE THE LEAK DETECTION FUNCTION, PLEASE REFER TO THE INSTALLATION MANUAL.
4. MODEL NAME
5. MANUFACTURING NUMBER
4. AFTER FILLING IN THIS TABLE, PLEASE PUT IT ON THE SWITCH BOX COVER.
3P328191-1
3P328192-1
HP
Øa
Øb
5
25,4
19,1
8
10
22,2
12
28,6
14
16
18
20
(a)
18+20
31,8
41,4
5
9,5
9,5
8
10
12
12,7
14
12,7
16
18
15,9
20
Tubos accesorios (mm)
Tubería de gas de alta
presión/baja presión
▪ Conexión delantera
ID Øa
ID Øb
▪ Conexión inferior
ID Øa
OD Øb
(a)
Solo en combinación con el kit de tubería de conexión para
unidades exteriores múltiples.
3.5
Extracción del soporte de
transporte (solo para 14+16 CV)
El soporte de transporte instalado para proteger la unidad durante el
transporte debe retirarse. Siga los pasos descritos en la siguiente
figura.
AVISO
Si acciona la unidad con el soporte de transporte todavía
colocado, es posible que se produzcan vibraciones o
ruidos anómalos.
1 Afloje un poco el perno (a).
2 Retire el soporte de transporte (b) tal y como se muestra en la
figura de abajo.
3 Vuelva a apretar el perno de fijación (a).
(12.3 N·m)
3
3
1
1
2
2
2
2
(x2)
(x2)
a
3.6
Extracción del soporte de
transporte (solo para 18+20 CV)
El soporte de transporte instalado para proteger la unidad durante el
transporte debe retirarse. Siga los pasos descritos en la siguiente
figura.
AVISO
Si acciona la unidad con el soporte de transporte todavía
colocado, es posible que se produzcan vibraciones o
ruidos anómalos.
1 Afloje un poco el perno (a).
2 Retire el soporte de transporte (b) tal y como se muestra en la
figura de abajo.
3 Vuelva a apretar el perno de fijación (a).
4 Afloje un poco el perno (c).
5 Retire el perno (d) y el soporte de transporte (e).
6 Retire el soporte de transporte (e) tal y como se muestra en la
ilustración de abajo.
Guía de referencia para el instalador y el usuario
3 Acerca de la caja
HP
Øa
Øb
5
19,1
15,9
8
10
19,1
12
14
22,2
16
18
20
28,6
3
3
1
1
a
b
9