Register Number
Register Name
1438
QV
2000
Status
2002
PV
2004
SV
2006
TV
2008
QV
2100
Status
2102
PV
2104
SV
2106
TV
2108
QV
2200
Status
2202
PV
2204
SV
2206
TV
2208
QV
14.6 Datos de medición adicionales
Register Number
Register Name
2303
Measured distance float32
2305
Absolute echo am-
plitude
VEGAPULS C 21 • Protocolo Modbus y Levelmaster
Data type
Note
Access
float32
Quarternary Variable in Byte Order CDAB
ro
enum8
See Register 100
ro
float32
Primary Variable in Byte Order ABCD (Big Endian)
ro
float32
Secondary Variable in Byte Order ABCD (Big Endian)
ro
float32
Third Variable in Byte Order ABCD (Big Endian)
ro
float32
Quarternary Variable in Byte Order ABCD (Big Endian)
ro
enum8
See Register 100
ro
float32
Primary Variable in Byte Order DCBA (Little Endian)
ro
float32
Secondary Variable in Byte Order DCBA (Little Endian)
ro
float32
Third Variable in Byte Order ABCD DCBA (Little Endian)
ro
float32
Quarternary Variable in Byte Order DCBA (Little Endian)
ro
enum8
See Register 100
ro
float32
Primary Variable in Byte Order BACD (Middle Endian)
ro
float32
Secondary Variable in Byte Order BACD (Middle Endian)
ro
float32
Third Variable in Byte Order BACD (Middle Endian)
ro
float32
Quarternary Variable in Byte Order BACD (Middle Endian)
ro
Type
Note/Unit
Distance from the sensor to the liquid surface (m)
ro
float32
dB
ro
14 Anexo
55