5.9

Gas feeding

Explosion danger due to fuel leaks in the pres-
ence of a flammable source.
Precautions: avoid knocking, attrition, sparks and
heat.
Make sure that the fuel interception tap is closed
before performing any operation on the burner.
The fuel supply line must be installed by qualified
personnel, in compliance with current standards
and laws.
WARNING
The gas train must be connected to the gas connection
1)(Fig. 16), using the flange 2), gasket 3) and screws 4) supplied
with the burner.
The train can enter the burner from the right or left side, depend-
ing on which is the most convenient, see (Fig. 16).
The gas solenoids must be as close as possible to the burner to
ensure that the gas reaches the combustion head within the safe-
ty time of 3s.
Make sure that the pressure adjuster calibration range (colour of
the spring) comprises the pressure required by the burner.
Code
Model
3970144
MB-DLE 412
3970197
MB-DLE 412 CT
3970180
MB-DLE 415
3970198
MB-DLE 415 CT
3970181
MB-DLE 420
3970182
MB-DLE 420 CT
3970221
MBC-1200-SE -50
3970225
MBC-1200-SE-50 CT
Key (Tab. G)
C.T. = Checking device for gas valves seal:
- = Gas train without gas valve leak detection control
device; device that can be ordered separately and
assembled subsequently (see Column 7).
 = Train with seal checking device already assembled.
7
= Valve seal checking device VPS. Supplied separately
from gas train on request.
11
= Gas train/burner adaptor. Supplied separately from gas
train on request.
NOTE:
See the accompanying instructions for the adjustment of the

gas train.

Installation
Gas trains L
17
GB
5.9.1
Gas train
The train is type-approved in accordance with EN 676 and sup-
plied separately from the burner, with the code indicated in Tab. G.
Make sure that the gas train is properly installed
by checking for any fuel leaks.
Make sure that there are no gas leaks on the
WARNING
pipes between the gas meter and the burner.
Ø
C.T.
1"1/4"
-
1"1/4"
1"1/2
-
1"1/2
2"
-
2"
2"
-
2"
D505
7
11
Code
Code
3010123
3000843
3010123
3000843
3010123
3000843
3010123
3000843
3010123
-
-
-
3010123
-
-
-
Fig. 16
Tab. G
20040559

Publicidad

Capítulos

Tabla de contenido
loading

Este manual también es adecuado para:

832t20038459200384842003848220038486

Tabla de contenido