Alarms And Faults - Carrier 80AW1 Manual De Instalación

Ocultar thumbs Ver también para 80AW1:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 81
Maintenance

Alarms and faults

Fault name
displayed on the user
interface
Water temperature too high or pressure
DEF THER
too low
Not enough water fl ow in the heat
DEF FLOW
exchanger
FAIL MODE
One or more faults have occurred
Loss of signal from board 1PCB to board
DEF COM
2PCB (indoor unit)
DEF SENSOR R
Air temperature sensor in the Conex II
DEF SENSOR B
Water sensor TWB
DEF SENSOR E
Additional outdoor air temperature sensor
0
No Error
1
Lost communication to indoor unit
Water temperature entering heat
2
exchanger TWA (J6A)
4
Refrigerant temperature TC (J6B)
100
EEPROM Corrupt
DEF
MODULE
1000 Loss of signal from CDU
Water temperature exiting heat exchanger
2000
TWC (J6C)
8000 Outdoor air temperature (TO of the CDU)
24
80AW1- 80AWT - 80AW2
Description
If the pump (or pumps) sending water to the terminals is ON, the
water temperature in the electric heater vessel or buff er tank is too
high:
. water sensors can be out of order not properly placed
. fl oating setpoint curves can be set too high
. manual safety switch can be out of order or not correctly set
When the water temperature decreases, it is possible to remove
the alarm by pressing the reset button of the safety switch in the
control box.
If the pump (or pumps) sending water to the terminals is OFF, the
alarm comes from the fl oor heating manual reset proctection (TM)
or from the pressure switch (PS)
If the problem comes from TM:
. water sensors can be out of order or not properly in contac
. fl oating setpoint curves can be set too high
. TM can be out of order
When the problem is fi xed press the red button on TM to remove
the alarm
If the problem comes from PS (only for 80AW2 units)
. the pressure in the system might be too low: check for water leaks,
fi x them and fi ll the system up to the correct operating pressure
. the pressure switch might be out of order or not properly
connected
Clean the fi lter
Check if the pump is running
Check the water pump speed
Check the connection of the fl owswitch on the board 1PCB
Replace the fl owswitch
Check the user interface display for a description of the faults
Check the connection between board 1PCB and board 2PC in the
indoor unit control box
Change Conex II user interface
Check indoor temperature sensor (TWB)
Check the connection of the sensor to the board 2PCB
Check the outdoor air sensor
Check the connection of the sensor to the board 2PCB
Check the connection between boards 1PCB and 2PCB in the
indoor unit control box
Check indoor temperature sensor (TWA)
Check connection of the sensor to the board 1PCB
Check indoor temperature sensor (TC)
Check connection of the sensor to the board 1PCB
Change the board 1PCB
Check HV communication between board 1PCB and the CDU
Check connection J4 on board 1PCB
Check connection between board 1PCB and terminal block
Compressor case thermo Open
Check indoor temperature sensor (TWC)
Check connection to board 1PCB
Check outdoor temperature sensor (TO)
Check connection to the CDU board
Diagnostic and Solutions

Publicidad