6.4.4
Portable wet well installation
4
3
2
Fig. 6: Wet well installation; portable
20
Installation and electrical connection
WARNING
Danger of burning due to hot surfaces!
The motor housing can get hot during operation. It can lead to burns. Allow the pump to
cool down to ambient temperature after switching off!
WARNING
Separation of the pressure hose!
Separation or movement of the pressure hose can result in (serious) injuries. Attach pres-
sure hose securely to the outlet! Prevent buckling of the pressure hose.
NOTICE
Pumping problems due to water level being too low
If the fluid is lowered too much, separation of the volume flow may occur. Furthermore,
air cushions may form in the hydraulic system, resulting in undesirable behavior during
operation. The minimum permissible water level must reach up to the upper edge of the
hydraulics housing!
For portable installation, the pump must be equipped with a foot. The pump support foot
ensures the minimum ground clearance in the suction area and allows secure footing on a
firm foundation. Thus in this installation type, any positioning in the operating space/instal-
lation site is possible. To prevent sinking on soft surfaces, a hard base must be used at the
installation site. A pressure hose is connected on the pressure side. If operated for longer
periods of time, fix the pump firmly to floor. This prevents vibration and ensures quiet run-
ning and low wear.
CAUTION! If the motor emerges during operation, adhere to the operating mode for
non-immersed operation (S2-15, S3 10 %*)!
* If the required cooling of the motor is ensured before a re-activation, the operating mode
S3 25 % is permissible! To ensure the required cooling, the motor must be completely im-
mersed for at least 1 minute!
Work steps
1
Pump foot
5
2
Pipe elbow with hose connection or Storz pipe coupling
6
3
Storz hose coupling
S1
4
Pressure hose
5
Lifting equipment
6
Attachment point
Pump foot mounted.
S2 / S3
Pressure connection prepared: Pipe elbow mounted with hose connection or pipe elbow
1
with Storz coupling.
1. Attach lifting equipment to the attachment point of the pump with a shackle.
2. Raise pump and set down on the intended work place (pump chamber, pit).
3. Place pump on a firm foundation. CAUTION! Sinking must be prevented!
4. Lay the pressure hose and fasten it to a certain point (e.g. drainage). DANGER! Separa-
tion or movement of the pressure hose can lead to (serious) injury! Attach pressure
hose securely to the outlet.
5. Correctly route power supply cable. CAUTION! Do not damage power supply cable!