5. Commissioning, operation
5.2 Electrical mounting
Using a transmitter/digital display (option):
Observe the contents of the operating instructions for the transmitter/digital display (see
scope of delivery).
EN
Cable glands
Requirements for meeting ingress protection:
Only use cable glands within their indicated clamping range (cable diameter suitable for
the cable gland).
Do not use the lower clamping area with very soft cable types.
Only use round cables (if necessary, slightly oval in cross-section).
Do not twist the cable.
Repeated opening/closing is possible; however only if necessary, as it might have a
detrimental effect on the ingress protection
For cable with a pronounced cold-flow behaviour the gland must be fully tightened.

5.3 Electrical connection

CAUTION!
Danger of short circuit
Damage to cables, wires and connection points can lead to malfunction of
the instrument.
12
Avoid damaging the cables and wires. Fine-stranded leads with bare ends
must be finished with end splices.
WIKA operating instructions, models TRxx and TCxx