5.12.18 Checking the fan motor

The control box automatically detects the presence of the fan
motor and, in the event of a fault, it performs a lockout. The
lockout is indicated by the blinking of the LED (see paragraph
"Fault diagnostics - lockouts" on page 24).
5.12.19 Checking the faults of the gas valve and the
motor
The control box detects the presence of a fault in the valve and
motor controls, the fault is indicated by the blinking LED (see
paragraph "Fault diagnostics - lockouts" on page 24):
 if the anomaly is detected during the initialisation, the burner
goes into lockout.
 if the anomaly is detected during the pre-purging, the burner
goes into lockout.
 During a recycling, if the fault is detected, the burner does
not start and goes into lockout.
The fault is not detected if the burner is in lockout.
The sealing of the contact of the relay inside the motor's control
box is intercepted if the gas pressure switch is closed and the
motor is connected to the board.
The closing of the relay contact inside the gas valve control is
intercepted only with the motor on.

5.12.20 EEprom check

The control box automatically detects if EEprom memory of
micro-controller has failed and will perform a lockout. The lockout
is indicated by the blinking of the LED (see paragraph "Fault
diagnostics - lockouts" on page 24).

5.12.21 Ionisation current

The recommended minimum for operating the burner is 5 µA.
The burner normally supplies a higher current value, so that no
check is needed.
In any event, if you want to measure the ionisation current, you
need to open the connector (CN1)(Fig. 20) on the red wire and
insert a microammeter.

5.12.22 Post-purging

Post-purging is a function that allows you to maintain the air
purging even after the burner is switched off in the absence of the
heat request for a pre-set time.
The burner switches off the flame when the heat request
thermostat opens, and the fuel supply to the gas valve stops.
The post-purging function is not performed:
 after a lockout of the motor or valves;
 if the heat request is interrupted during pre-purging.
Installation
CN1
_
+
D4631
Fig. 20
Post-purging occurs:
 if the heat request is interrupted during the safety time;
 if the heat request is interrupted during normal operation;
 with all types of lockout.
NOTE:
If during post-purging there is an extraneous light or a parasite
flame the burner goes into lockout after 25 seconds.
If during post-purging there is a new heat request, the post-
purging time is halted, the fan motor stops and a new burner
operating cycle starts.

5.12.23 Continuous purging

Continuous purging is a function that maintains the air ventilation
independently of the request for burner ignition.
From the moment when it is set, the motor remains in operation
both when the limit thermostat (TL) is not switched over (burner
switched off), and when the burner is in lockout.
With the commutation of the limit thermostat (TL) the motor stops
for the standby time of 2 seconds, the successive control of the
air pressure switch and the start of a new burner operation cycle.
 If during continuous purging when there is no heat request a
parasite flame is detected, the motor stays on and a fault is
signalled. The burner reaches the lockout condition after 25
seconds.
 If during continuous purging a parasite flame is detected, the
motor stays on but if a heat request occurs the motor is
switched off, the motor is not started after the standby (2sec)
if the parasite flame persists; the burner reaches the lockout
condition after 25 seconds. After the lockout has been reset
the motor is restarted.
 The motor stays on even in a lockout.
 Continuous purging is interrupted if an internal fault is
detected that brings the burner to the lockout condition
(eeprom, motor, gas valve).
SO