TO BE ABLE TO START THE GENERATOR. THE
BATTERY POWER SAVING MODE UNLESS THE
FUEL SELECTOR SWITCH IS TURNED TO THE
"OFF" POSITION AND THEN TURNED BACK TO
THE "GAS" OR "LPG" POSITION. See Indicator
light-Battery power Saving Mode section for
more information.
Engine Start Switch – Used to start engine from
3
the starter motor(Electric start model only). To
start engine, press and hold the switch in the
"START"(ll) position, the
engine will crank and attempt to start. When
the engine starts, release the switch to the drawn from this 120 Volt receptacle. "RUN"(l) position.
3-1 Data-Minder(Multi-Meter) – Push the
4
SELECT button to show the Voltage, Hertz and
running hours.
Maximum 30 Amp current maybe drawn from
this 120/240 Volt receptacle.
Ground Terminal – Consult an electrician for
9
local grounding regulations.
120/240V, 50A – (NEMA 14-50R) Supplies
10
electrical power for the operation of 120/240
Volt AC, 50Amp, single phase. Maximum full
load current may be drawn from this
receptacle. If other receptacles are used at
the same time, total power used must be
kept within nameplate.
Outlet Cover - Protect the receptacles from
11
dust and debris.
LPG Hose Connector(Inlet) – Used to
12
connect LPG hose to generator.
120VAC, 20AMP GFCI RECEPTACLE
This unit is equipped with a ground fault circuit
interrupter (GFCI). This device meets applicable
federal, state and local codes .
English
Circuit Interrupter) – (NEMA 5-20R)
This receptacle is rated so that a total of 20 amps may
be drawn regardless of whether both halves or just
one receptacle is used.
Ground Fault Circuit Interrupter conforms to UL 943,
and NEC requirements. This device protects you
against hazardous electrical shock that may be caused
if your body becomes a path through which electricity
travels to reach ground. This could happen when you
touch an appliance or cord that is " live " through faulty
mechanism, damp or worn insulation, etc.
120V, 30A Twist-Lock – (NEMA L5-30R)
7
Maximum full load 30 Amp current may be
120/240V, 30A Twist-Lock – (NEMA L14-30R)
8
A GFCI receptacle is different from conventional
Testing the GFCI: Test the GFCI outlet every
month as follows:
1. Plug a test lamp into the receptacle.
2. Start the generator, the test lamp should be
on.3. Press the "Test" button located on the
front of the receptacle to trip the device.
4.
This should stop the flow of electricity
making the lamp shut off. The GFCI's indicator
light comes off.
5.
To restore the flow of electricity, press
the "RESET" button on the front of the
receptacle. If the GFCI does not perform in this
manner, do not use the receptacle. Contact a
local service dealer or costumer service.
6.
This outlet is protected against
overload by a 20A push-to-reset circuit breaker.
Use the outlet to power 120V AC, single-phase,
60 Hz, electrical loads requiring up to a
combined 2400 watts (2.4 kW) or 20 amps of
current.
Customer Service: 1-844-FIRMAN1Page 13