T-100
ENGLISH
PTB 09 ATEX 1043 U
II 2 G Ex e II
II 2 D Ex tD A21 IP66
IECEx PTB 09.0023 U
Ex e II
Ex tD A21 IP66
TC RU C-BE.MЮ62.B.02853
1Ex e IIC
ATEX and IECx approved:
Rated voltage: 
480 Vac (when used with VPL4)
277 Vac (when used with 230 Vac heating cables)
Ambient temperature: -50°C to +56°C
Maximum pipe temperature:
Heater type
T
max
BTV
65°C
QTVR
110°C
XTV
121°C
KTV
150°C
VPL
See tables below
Cable
230V
5VPL2-CT
230°C
10VPL2-CT
210°C
15VPL2-CT
180°C
20VPL2-CT
150°C
VPL: maximum pipe temperature in dependence
of heat type and voltage
230 Vac
5VPL2-CT
230°C
10VPL2-CT
210°C
15VPL2-CT
180°C
20VPL2-CT
150°C
285V
5VPL4-CT
230°C
10VPL4-CT
215°C
15VPL4-CT
195°C
20VPL4-CT
150°C
US approved only
Rated voltage: 
277 Vac
Ambient temperature:
–40°C to +40°C
Cable
5VPL2-CT
10VPL2-CT
15VPL2-CT
20VPL2-CT
Installation instruction for splice and Tee connection kit T-100. For use with all nVent RAYCHEM BTV-, QTVR-,
XTV-, KTV- and VPL-heat ing cables.
WARNING: To prevent electrical shock or fire, this product must be installed correctly. Water ingress must be avoided
before and during the installation.
Ground fault equipment protection must be used on each heating cable circuit as arcing may not be stopped by conventional
circuit breakers. Before installing this product, read the instructions completely. Do not use substitute parts or vinyl electrical
tape. Avoid skin and eye contact with sealing grease. Consult RAYCHEM safety datasheet VEN0058.
4 | nVent.com
All manuals and user guides at all-guides.com
CLI, ZN1, AEx e II*
Ex e II T*
Except VPL
(1)
* For systems temperature code, see heating cable or design
documentation
continuous
254 Vac
277 Vac
225°C
225°C
200°C
195°C
145°C
105°C
Not allowed
400 Vac
480 Vac
230°C
225°C
215°C
195°C
195°C
105°C
150°C
150°C
208V
235°C
230°C
200°C
150°C
Class I, Div. 2, Groups A, B, C, D
F M
(1)
APPROVED
Class II, Div. 1 and 2, Groups E, F, G
®
Class III
Temp Code*
BTV - IEx 09.0004X
QTVR - IEx 09.0006X
XTV - IEx 09.0005X
VPL
- IEx 09.0007X
T
intermittent
max
1000h cumulative
85°C
110°C
250°C
250°C
254V
225°C
200°C
145°C
Not allowed
VPL: maximum current in dependence
of pipe temperature
≤ 150°C
≤ 180°C
30 A
25 A
30 A
25 A
30 A
25 A
30 A
-
≤ 150°C
≤ 180°C
30 A
25 A
30 A
25 A
30 A
25 A
30 A
-
240V
277V
230°C
255°C
205°C
195°C
160°C
105°C
150°C
Not allowed
T
power off
max
260°C
≤ 230°C
20 A
20 A
-
-
≤ 230°C
20 A
20 A
-
-