Descargar Imprimir esta página

Characteristics; Factory Settings - Sime AQUA HE 25 ErP BE Instrucciones Para El Instalador

Publicidad

Idiomas disponibles

Idiomas disponibles

3

CHARACTERISTICS

3.1
COMBUSTION CHAMBER
DIMENSIONS (fig. 10)
The. combustion. chamber. is. a. direct.
passage.type.and.is.conform.to.the.EN.
303-3. standard. annex. E.. The. dimen-
sions. are. shown. in. fig.. 10.. An. ade-
quate.protection.panel.is.mounted.on.
the.inside.wall.of.the.rear.head.of.all.
the.models.
L
.
mm.
25 ErP BE
405.
35 ErP BE
505.
3.2
SYSTEM AVAILABLE HEAD
(fig. 11)
The. head. available. for. the. heating.
plant.is.shown.as.a.function.of.the.flow.
in.graph.in.fig..11.
3.3
HIGH EFFICIENCY PUMP
(fig. 11/a)
Press.the.button.(4).briefly.(about.1.sec-
ond).to.select.the.pump.operating.mode..
The.relative.LEDs.will.indicate.each.time.
the.adjustment.mode.(2).and.the.charac-
teristic.curves.set.(3)...
Point. 3.3.4. reports. the. possible. combi-
nations.and.their.meaning..
When. the. LED. (1). signals. a. fault,. the.
pump.stops.and.attempts.to.run.restart.
cycles..If.the.fault.is.solved,.the.pump.re-
starts.automatically.
3.3.1
Venting the pump
The. pump. venting. function. is. activated.
by.pressing.the.button.(4).for.a.long.time.
(3.seconds).and.vents.automatically.
3.3.2

Factory settings

The.factory.setting.is.activated.by.press-
ing.and.holding.the.button.(4).and.disa-
bling. the. pump.. When. the. pump. is. re-
started,.it.will.work.with.factory.settings.
(delivery.state).
3.3.3
Manual restart
When. a. lockout. is. detected,. the. pump.
tries. to. start. automatically.. If. the. pump.
does. not. restart,. restart. manually. by.
pressing. the. button. (4). for. a. long. time.
(5.seconds),.then.release.it..The.restart.
80
Volume
3
dm
24,0
30,5
600.(58,8)
500.(49,0)
400.(39,2)
300.(29,4)
200.(19,6)
100.(9,8)
function.is.activated.for.a.maximum.of.10.
minutes..After.the.restart,.the.LED.indi-
270
594.(58,21)
601.(58,89)
535.(52,43)
0
200
400
600
L
492.(48,21)
455.(44,59)
400.(39,20)
321.(31,45)
239.(23,42)
800
1000
1200
1400
1600
FLOW.RATE.(l/h)
PORTATA.(l/h)
1
2
3
4
cation.shows.the.previously.set.values..
If.the.fault.persists,.replace.the.pump..
Fig..10
1800
Fig..11
Fig..11/a

Publicidad

loading

Este manual también es adecuado para:

Aqua he 35 erp beAqua he 25 inox erpAqua he be 35 inox erp be