2.7. Connecting the input contacts and FAIL relay

ATTENTION: ONLY IF THE DC-700ETH/T IS EQUIPPED
WITH THE OPTIONAL MODULE CC-700CC
(THREE INPUT CONTACTS AND FAIL INDICATOR RELAY)

2.7.1. Input contacts I1, I2 and I3

The CC-700CC module has three input contacts,
configurable via Call Point or Call Point Configurator
software.
Available functionalities:
- -Activation of the Emergency Mode and
activating the Warning or Evacuation message
configured. Configurable activation by pulse or
level.
- Emergency Mode cancellation. Activation by
pulse.
- Alarm notification. Activation by level.
- Activation
of
a
pre-recorded
configurable by pulse or level.
Through the software you can also configure the
idle state of each contact (NC/NO) and the
detection time of the activation pulse of the input
contacts
(0-50-100-200-300-400-500-1000-1500-
2000 milliseconds).
For connection follow DIAGRAM A. If you want the
system to monitor the contact connection, follow
DIAGRAM B.

2.7.2. FAIL Relay

Relay used to indicate a system failure.
If the COM contact is linked to the NO contact, it
indicates that there are no alarms in the system. If
on the other hand, COM is linked to NC, it indicates
that the equipment is switched off or that alarms
were detected.
Characteristics
Maximum DC charge current: 150 mA
Maximum DC or AC peak charge voltage: 350 V
Configuration and User Manual. Version 5.2.001
DC-700ETH/T.
message,
R+D Department
Configuration and user's manual
DIAGRAMA A. INPUT CONTACT CONNECTION
WITHOUT SURVEILLANCE
DIAGRAM B.
INPUT CONTACT CONNECTION
WITH SURVEILLANCE
FAIL RELAY STATUS
Device is turned off
or alarms detected
2. CONNECTION
No alarms