4.5 How to mount the boom
WARNING All balancing oeprations must be performed with factory operator confi guration and the control panel turned off.
Before starting to mount the boom, check the boom length accordingly to the width of the opening and, if necessary, cut it by using
proper equipment.
WARNING For safety purposes, DEA system recommends that two people carry out the operation. This can avoid dangerous situations
and to operate even under unfavourable conditions (e.g. in the presence of strong wind, sloping ground, etc.). Please note that acci-
dentally dropping the rod during assembly can cause serious damage to the mechanics of the barrier.
Then proceed as follows:
• Ensure that the boom-holder is positioned vertically (springs fully discharged);
• Unscrew and remove the lower fi xing screw of the spring unit (Pic. 5);
• Unlock the operator;
• Rotate the boom-holder 90° clockwise and lock the operator in this position (Pic. 11);
• Mounting the boom in a horizontal position (Pic. 12);
• Unlock the operator;
• Lift the boom and at around 45°, re-lock the operator;
• Bring the boom to the complete open position (Pic. 13) until the lock key falls into place (Pic. 14);
WARNING: When lifting, the boom is uncontrolled and if dropped it may cause serious damage to the mechanics.
• Refi t the lower fi xing screw of the spring unit;
• Perform a balancing test by verifying that moving the boom to 45°, and letting go, it should balance uncontrolled movements (other-
wise adjust). Next, tighten the nut (Pic. 15);
• Fit the cover of the boom-holder.
4.6 Limit-switches (Pic. 16)
All PASS N models are equipped with mechanical stops which allow the adjustment of the boom run while closing and opening.
Release the operator and adjust the mechanical stops by loosening the lock nut (A) and then adjust the hexagonal head screw (B).
Then tighten the lock nut (A).
5 ELECTRICAL CONNECTIONS
In case you have to operate on the control panel (for wiring, adjustments etc...), remove the circuit support plate. To do this, proceed
as follows (Pic. 17):
• unscrew the fi xing screws of the control panel holder plate, without removing them;
• Unhook the plate of the barrier case as shown;
• Move the control panel box into a most comfortable position and perform the necessary tasks;
Run the motor connections following the wiring diagrams.
WARNING For adequate electrical safety, keep low safety voltage wires (controls, electro-locks, antenna, auxiliary power) clearly separate
from 230V ~ power wires (minimum 4 mm in air or 1 mm via supplementary insulation) placing them in plastic raceways and securing
them with adequate clamps near terminal boards.
WARNING For connection to the mains, use a multipolar cable having a minimum section 3x1,5 mm² and complying with the current
regulations. For connecting the motors, use a minimum cross section 1,5 mm² cable and complying with the current regulations. As
an example, if the cable is out side (outdoor), must be at least equal to H05RN-F, whereas if it (in a raceway), must be at least equal to
H05VV-F.
WARNING All wires must be striped and unsheathed in the immediate vicinity of terminals. Keep wires slightly longer to subsequently
eliminate any excess.
WARNING Maintain the ground conductor at a major length respect the active conductors so that, if the cable exit from its fi xing housing,
the active conductors tighten up as fi rst.
WARNING To connect the encoder to the control panel, use only a dedicated cable 3x0,75mm
Program the control board to complete all adjustments. It is now possible to supply a complete installation in compliance with all stan-
dards required for gate automation. See the instructions provided with the control panel to be connected.
Finally, verify that all adjustments operations have been correctly performed and that safety devices and unlocking device properly
work.
PASS24NET/N/L (4/5 m)
PASS24NET/N/V (3 m)
PASS24NET/N/VR (4 m)
Recommended values for standard "TYPE 03 - Barriers" 24V
Running speed
Slowdown speed
(P032 - P033)
(P031 - P034)
100%
30%
80%
25%
80%
25%
.
2
Slowdown
Soft start
duration
(P054)
(P035 - P036)
15%
0
45%
0
45%
0
PASS N
Facilitation
Stop margin
release
(P058 - P059)
(P057)
2
10
1
3
1
3