V/f lin. --> quad.
XXX [%]
V
V nom mot
V boost
Rotation sense
---> / <---
MOTOR TUNING
press ENT
Mot. resistance
Rs=XXX.XX [Ohm]
Mot. inductance
Ls=XXX.XX [mH]
FOC dynamic
XXX
Autorestart
ON/OFF
28
V / f characteristic with which IPFC feeds the engine. The linear
characteristic corresponds to constant torque with variable speed. The
quadratic characteristic is normally used with centrifugal pumps. The
85 %
selection of torque characteristic should be done ensuring a smooth
operation, a reduction of energy consumption and a lower level of heat
and acoustic noise.
f min mot
If, during the test, the motor runs in reverse, it is possible to change the
--->
wiring sequence via software without physically changing wires at the
terminals.
If the device is "FOC-ready", motor calibration must be carried out
before commissioning.
Carefully read the pertinent chapter.
Manual setting of the stator resistance.
Manual setting of the stator inductance.
Setting of the control dynamic of the FOC algorithm.
If ON is selected, after a lack of voltage, IPFC returns to its normal
status; if IPFC was powering the pump before the voltage drop, it
OFF
resumes powering the pump automatically.
Warning, review the advice in chapter 1.
f nom mot
f