Slave setup
Follow Master setup until point 11.
In case of failure of master in a Combo system, will be replaced by slave. As a consequence, all parameters must be setup
independently on each inverter, master mode.
1. Set:
Address
XX
2. Press STOP (red button).
3. In the Motor parameters verify that Autorestart is set ON.
4. Press STOP (red button).
5. Press STOP again.
Whenever the user accesses the Menu screen of the IPFC master, the communication between IPFCs is automatically
interrupted.
In case of alarm or failure of a pump in a Combo system, this pump's operation will be replaced (temporary or
permanently) by another pump.
In case of failure of master in a Combo system, it will be replaced by the next slave after about 1 minute. In order to
enable master replacement Autorestart must be set ON in each slaves.
36
IPFC's address in parallel operation.
01 --> 07: IPFC slaves