Descargar Imprimir esta página

Connectivity Parameters; Protections And Alarms - Pentax IPFC 109 Manual De Instrucciones

Ocultar thumbs Ver también para IPFC 109:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Parameter
Dig.In.2/3 delay
[s]

6.8 Connectivity parameters

Parameters
MODBUS address
XXX
MODBUS baudrate
XXXXX [bps]
MODBUS data format
XXXXX

7. Protections and alarms

Anytime a protection occurs a blinking message is displayed together with an audible alarm; on STATUS in the initial view, the
protection is displayed; by pressing the STOP button. Only from this position (STATUS) in the initial view is it possible to try
to reset the alarm; if IPFC does not reset the alarm it is displayed again together an audible sound.
ALARM MESSAGE
OVERCURRENT MOT.
UNDER VOLTAGE
OVER VOLTAGE
OVER TEMP. INV.
NO LOAD
30
Default
Digital input IN2 & IN3 delay.
3
Digital input IN1 has 1 second fix delay.
Default
1
MODBUS address from 1 to 247
9600
MODBUS baudrate from 1200 bps to 57600 bps
RTU N81
MODBUS data format: RTU N81, RTU N82, RTU E81, ETU O81
ALARM DESCRIPTION
Motor overload: input current of the
motor is higher than the rated motor
current setting parameter.
Motor voltage drop caused by the inverter
causes the motor input current to be
higher than rated. Contact motor
manufacturer to check if motor is capable
of accepting this current.
Supply voltage too low
Supply voltage too high
Inverter over temperature
No load
Description
Description
POSSIBILE SOLUTIONS
 Make sure that the motor current setting
parameter is higher than rated.
 Check other possible causes of over current
Check possible causes of undervoltage
Check possible causes of overvoltage
 Make sure than ambient temperature is
less than 40 °C (104 °F).
 Check if auxiliary cooling fan is working
properly and if mounting space is adequate
for proper cooling.
 Reduce the PWM value (Advance
Parameter Menu)
 Check if load is properly connected to the
IPFC terminals

Publicidad

loading