4 Electrical installation

Danger of death through electric shock!
Touching live parts can result in death.
All electrical work must be carried out by a quali-
fied electrician while observing the VDE regulations,
national and other regulations.
Increased leakage current!
Establish the PE connection first!
Do not open the Solar Inverter housing! The unit
still carries life-threatening voltage for approx. five
BG
minutes internally and at the connection terminals
of the PV generator following disconnection from
the grid and the solar generator.
CS
DE
1
2
EL
EN
1 Terminals for solar generator string 1
2 Terminals for solar generator string 2
3 DC load break switch
ES
4 AC terminal
DC connection
FR
1 Strip the voltage-free line.
IT
8
2 Use the Tyco Solarlok hand crimping pliers for
NL
the circular contact.
PT
SL
48
– +
3
4
+
+
3 Slide the cable gland onto the cable and engage
the contact in the connector housing.
4 Tighten the cable gland with 1.5 Nm.
5 Connect the socket and connector.
For the system to be locked properly the lock-
ing hooks must be recessed flush in the mating
piece.
CAUTION
The connectors must not be separated under load.
First interrupt the circuit at a suitable point.
Release the locking device by pressing on the rib-
bing of the locking hooks and pulling.