Unit Power Supply - Airwell AW-WHPMA04-H91 Manual De Instalación

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

MCA : Max. Circuit Amps. (A)
TOCA : Total Over-current Amps. (A)
MFA : Max. Fuse Amps. (A)
MSC : Max. Starting Amps. (A)
RLA : In nominal cooling or heating test condition,the input Amps of compressor where MAX. Hz
can operate Rated Load Amps. (A)
KW : Rated Motor Output
FLA : Full Load Amps. (A)
9.7.5 Remove the switch box cover
Unit
4kW
6kW
Maximum
overcurrent
18
18
protector(MOP)(A)
2
4.0
4.0
Wiring size(mm
)
L
N
LPS
L N

UNIT POWER SUPPLY

UNIT POWER SUPPLY
1-phase
The ground fault circuit interrupter must be 1 high-speed type of 30mA(<0.1s). Please use 3-core shielded wire.
The default of backup heater is option 3 (for 9kW backup heater). If 3kW or 6kW backup heater is needed, please
ask professional installer to change the Dip switch of S1 to option 1(for 3kW backup heater) or option 2(for 6kW backup
heater), refer to 10.2.1 FUNCTION SETTING.
Stated values are maximum values (see electrical data for exact values).
NOTE
8kW
10kW
12kW
32
32
43
8.0
8.0
10.0
L1
LPS
LPS
L N
UNIT POWER SUPPLY
1-phase
40
14kW
16kW
12kW 3-PH 14kW 3-PH 16kW 3-PH
43
43
27
10.0
10.0
4.0
L2 L3
N
N
L1
L2
L3
UNIT POWER SUPPLY
3-phase
27
27
4.0
4.0
L1
L2 L3
N
LPS
N
L1
L2
L3
3-phase