Descargar Imprimir esta página

Calibrating The Oil Scales - Waeco ASC 6300 G LE Instrucciones De Uso

Ocultar thumbs Ver también para ASC 6300 G LE:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

EN
5. Enter the password
6. Enter the hose length in centimetres.
7. Press
ENTER
14.4

Calibrating the oil scales

Note In order for the oil quantities and the UV additive to be measured correctly, the zero point of the
scales must be checked regularly and reset if necessary. Resetting is necessary:
• If the quantity in a container deviates by more than 10 ml from the target value
• If the A/C service unit has been shaken, for example during transport on bumpy roads
• Every four to six weeks
1. In the basic menu use the cursor keys
Short selection
Free selection
Other selections
ENTER-OK
2. Press
ENTER
3. Use the cursor keys
Int. vessel filling
Flushing
Reset scales.
Service.
You are then prompted to remove the containers from the scale:
Remove the 3 Oil/UV
glasses from scales.
ENTER-OK STOP-EXIT
30
.
7732
to confirm.
to confirm.
or
to select Reset scales.
or
to select Other selections.
 

Publicidad

loading

Este manual también es adecuado para:

Asc 6400 g leAsc 6300 gAsc 6400 g91033031079103303108