Changing The Dryer Filter - Waeco ASC 6300 G LE Instrucciones De Uso

Ocultar thumbs Ver también para ASC 6300 G LE:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

 
4. To check the zero point of the scales for oil and UV additive, open the cover (13) on the left side and take the
containers off the catches:
• Container for fresh oil (10)
• Container for UV additive (11)
• Drained oil receptacle (12)
5. When the scales are relieved, press
will flash. Once you have set the zero point, the selection menu for the scales appears again.
6. Return the containers to the operating positions: Reattach the containers for oil (10) and (12) and for the UV
additive (11) to the snap locks and close the cover (13).
7. Press
STOP
twice to access the standby menu.
14.5

Changing the dryer filter

1. In the basic menu use the cursor keys
Short selection
Free selection
Other selections
ENTER-OK
2. Press
ENTER
3. Skip the query requesting CAR DATA.
4. Select Rec/Recycling phase.
5. Set the Pressure increase Test time to
6. Press
ENTER
7. Deselect Vacuum phase using
8. Press
ENTER
9. Deselect Filling phase using
10. Press
ENTER
ENTER
to confirm.
to confirm.
.
No
to confirm.
.
No
to confirm.
to confirm. The prompt to remove the containers from the scale
or
to select Free selection.
.
1
EN
31