The operating/ambient conditions are 5 ... 55 °C; IP 54/64; 93 % rel.
humidity.
ƒ
Ambient temperatures below 35 °C have a positive effect on battery
lifetime.
If the flow sensor is insulated with the pipeline, the calculator
must be accessible.
Detailed user guide available at https://www.diehl.com/metering/en/
support-center/download-center/
The Software IZAR@Mobile2 is used for reading out data and configura-
tion and can be downloaded from the Internet under: https://www.diehl.
com/metering/en/support-center/download-center/
Changing of communication relevant parameters can result in
the loss of OMS certification.
2.
Transport and storage
Unpacking
Energy meters are measuring devices and must be handled with care.
To protect against damage and soiling, they should only be unpacked
immediately prior to installation.
Transport
The transport of the meter is permitted only in the original package.
When sending wireless measuring instruments / components by
air, disable the wireless (place in aircraft mode) before shipping.
3.
Installation of energy meter (fig. I)
ƒ
Depending on the design and application (heat or cooling meter), the
energy meter is installed in either the hot or cold line of the system.
ƒ
The flow sensor must be installed so that the flow direction matches
the arrow direction on the sensor.