Greengate
Bringing the Room Controller Online
The Room Controller is pre-programmed and ready for operation out-of-the-box. If no adjustments are done, the unit will
operate from the GPCS, daylighting and wallstations.
To obtain maximum energy efficiency and occupant satisfaction, we recommend that you complete this short checklist to
verify the unit is operating optimally for the space being controlled.
1.
Initial Power Up Response
Apply power to the Room Controller
Verify that all lighting loads turn on to full for 3 seconds before beginning normal operation
2.
Verify Wallstation Operation
Check each wallstation for proper operation of intended loads
The grid beginning on page 16, outlines the pre-programmed functions of the wallstation buttons. If buttons do not operate as intended,
ensure that all circuiting is routed properly for your intended application and that stations are connected to the proper Click & Go port
3.
Verify Greengate Patient Control Station (GPCS) Operation
Check the GPCS controller for proper operation of intended loads
The grid beginning on page 17 outlines the pre-programmed functions of the Greengate Patient Control Station. If buttons do not operate as
intended, ensure that all circuiting is routed properly for your intended application and the GPCS wiring is connected to the correct terminals
on the Room Controller.
4.
Set Minimum and Maximum Trim levels
Trim levels have been preset to approximately 90% maximum. Additional energy savings can be gained by adjusting the trim further if
electric
lighting contribution is over the target illuminance for the space
Locate the position of the trim level adjustment dials on the Room Controller
Trim levels are being adjusted at night or shades have been used to darken the space during daylight hours
Using the wallstations, turn ON all controlled lighting. For fluorescent lighting loads, wait one minute to allow lamps to warm up
Using a small screwdriver, twist the maximum trim dial counter clockwise, then fully clockwise again. The lights will go full bright
and the Room Controller will enter adjustment mode
Turn the maximum trim adjustment dial counter-clockwise in small increments until the light level is at the desired maximum level
Turn the minimum trim dial clockwise then fully counter clockwise. The light level in the room will go full dim
Turn the minimum trim dial clockwise in small increments until you begin to notice the light level increasing in the monitored
space, then turn the dial slightly counter clockwise from where this change begins
Save the new trim settings and go back to normal operation by pressing the "All OFF" button on any wallstation. If "All OFF" is not
pressed, the controller will automatically save these settings after two minutes
9850-000366-04 page 13
October 2021
Room Controller for Healthcare
Switchpack
White
Red
Receptacle
BMS/Out
Black
Sensors
Green
Sensors
Slider
Station
Wallstations
-
A/V
Mode
+
-
Demand
Response
+
-
Alert
+
Mode
-
Time
Clock
+
Energy Options DIP Switch
Demand Response
Occupancy
Not Used
1 2
3
4
Default 10%
Occ
20%
Vac (default)
30%
40%
0-10V Dimming Outputs
-
-
-
+
+
+
Dimmer 3
Dimmer 2
Dimmer 1
Dimmer 3
-
Dimmer 2
-
Dimmer 1
-
+
+
+
0-10V Dimming
www.cooperlighting.com