Connecting 0-10V Load Wiring
The RC3DEHC models allow for connection to up to three
0-10V dimming zones. For optimal operation from the
Greengate Patient Control Station, dimming zones and relay
loads should operate as the same zone. There may be some
exceptions depending on the intent of the application.
Refer to your lighting layout and/or diagram on the Room
Controller QuicKit box for the suggested 0-10V zoning for
your application.
Route the 0-10V purple and pink* wires through one of
the provided conduit knockouts in the low voltage section.
0-10V terminal blocks are removable for ease of wiring.
Connect the 0-10V purple wire to the positive location and
the pink* wire to the negative location on the first dimmer
terminal block. Repeat for additional dimming zones.
(for Example Purposes Only)
Load 1
Dimmer 1
Load 2
Dimmer 2
Exam
Lighting
Load 3
Dimmer 3
White
Red
Black
Green
-
A/V
+
Mode
-
Demand
+
Response
-
Alert
+
Mode
-
Time
Clock
+
Energy Options DIP Switch
Demand Response
Occupancy
1
2
Default 10%
Occ
20%
Vac (default)
30%
40%
0-10V Dimming Outputs
-
+
+
Dimmer 3
Dimmer 2
For daylight dimming applications,
N
ote:
any fixture wired to the same 0-10V
dimming zone will dim together.
Although out-of-the-box all dimmers
may dim from daylighting control, it is
possible to reset the daylighting to dim
strategic zones while others respond
only to manual raise lower commands.
For example, in the topology shown
above, daylight dimming may not be
desired for the exam or reading lighting
while the general lighting responds to
the daylight sensor.
9850-000366-04 page 5
October 2021
Sample Load Zoning
General
Lighting
6
Switchpack
Receptacle
BMS/Out
5
Sensors
Sensors
Slider
Station
4
Wallstations
3
2
1
Not Used
3
4
-
-
+
Dimmer 1
Dimmer 3
-
Dimmer 2
-
Dimmer 1
-
+
+
+
0-10V Dimming
Dimmer 3 Dimmer 2 Dimmer 1
-
-
-
+
+
+
0-10V Dimming
0-10V Pink* (-)
0-10V Violet (+)
Zone Wallstations and Scene Wallstations
Specifications
Voltage
Electrical
Connections
Installation
Operating Environment
Room Controller for Healthcare
General
Exam
Reading
Raise
Lower
All OFF
24 VDC supplied from Room
Controller
Class 2, LPS
Two onboard QuickConnect ports
Standard decorator opening
32° F to 104° F (0° to 40° C)
For indoor use only.
www.cooperlighting.com