Greengate
Daylight Sensor/IR Receiver
The Room Controller connects to one daylight sensor for multi-zone
dimming control in the RC3DEHC models.
Specifications
Voltage
Electrical
Light Sensor Range
Low
High
Direct Sun
Connections
Operating Environment
Mounting
The daylight sensor can be mounted to a ceiling tile or
fixture using the threaded post and locking washer over
materials up to a 0.75" thickness. The accessory mounting
bracket (DSCM-MT) allows the daylight sensor to be
mounted to a hard wall.
Ensure the daylight sensor is not obstructed and is not
●
looking directly at electric lighting
For skylights that contain motor controls, ensure the
●
daylight sensor is mounted below the daylight blocking
mechanism
Remember to adjust the sensor head to point the arrow
●
and lens in the correct position
Ensure the daylight sensor is not looking out the window
●
or skylight
9850-000366-04 page 9
October 2021
24 VDC supplied from Room
Controller
Class 2, LPS
3-300 lux
30-3000 lux
300-30000 lux
Sensor has a Click & Go ready
connector to a provided
GGRC-COUPLER.
32° F to 104° F (0° to 40° C)
For indoor use only.
Mount the daylight sensor one to two times
For narrower spaces mount the daylight
the window height from the window wall.
sensor near the window with the sensor
Position the sensor so its lens and arrow is
lens and arrow facing away from the
pointed toward the window.
window and pointing into the space.
60°
Area Viewed by
Daylight Sensor
Ceiling Location
Narrow Location
Locking Washer
Daylight Sensor
Viewing Lens
Room Controller for Healthcare
Area Viewed
by Daylight
60°
Sensor
60°
For skylights mount the
daylight sensor on the south
wall of the skylight well so
that the lens is aimed at the
north wall, with the arrow
Area Viewed by
and lens pointed up.
Daylight Sensor
Skylight Location
Sensor Cable to Coupler
(GGRC-COUPLER)
Threaded
Mounting Post
Ceiling
Adjustable Daylight
Sensor Dome