Room Controller for Healthcare
Load Wiring
Before Connecting Circuits:
1.
Connect lighting load wiring directly to the circuit breaker to ensure there are no shorts or miswires.
2.
For any 0-10V dimmable loads, separate the purple and pink* leads for each zone controlled. All lighting loads should be
at full bright output.
3.
Isolate one dimming zone and temporarily connect the purple and pink* 0-10V leads together.
4.
Verify that the controlled zone dims to its lowest output level, then label the zone wiring for easy identification.
Disconnect the 0-10V leads for the zone under test and then repeat for remaining dimming zones.
White/Black = 120V Neutral
White/Orange = 277V Neutral
Connect Neutral for Appropriate Voltage.
Emergency
Panel Neutral
Emergency Line In
(120V or 277V)
Normal Power Connections
The feeding circuit will provide power to the controlled
loads as well as to the room controller's microprocessor.
The maximum combined load of the three relays onboard
the room controller should not exceed 20A.
Connect line voltage wiring to the provided leads, matching
your room configuration to load 1, 2 and 3 according to
your lighting layout and/or diagram on the Room Controller
QuicKit.
www.cooperlighting.com
ALL MODELS
Yellow = Load 1 Out
Load 1
Red = Load 2 Out
Load 2
Purple = Load 3 Out
Load 3
Emergency
Load
Blue = Emergency Line In
RC3DE MODEL ONLY
CAUTION
Line In
Neutral
(120V or 277V)
Cap OFF all Unused Leads
OR
Blue = Room Line In
Black = Power Supply Line In
White
Switchpack
Receptacle
Red
BMS/Out
Black
Sensors
Green
Sensors
Slider
Station
Wallstations
-
A/V
+
Mode
-
Demand
+
Response
-
Alert
+
Mode
-
Time
+
Clock
Energy Options DIP Switch
Demand Response
Occupancy
Not Used
1
2
3
4
Default 10%
Occ
20%
Vac (default)
30%
40%
0-10V Dimming Outputs
-
-
-
+
+
+
Dimmer 3
Dimmer 2
Dimmer 1
Yellow = Emergency Load Out
Connecting Emergency Power Line Voltage
The RC3DEHC model supports a 3A emergency relay. This
is a UL 924 listed solution for emergency lighting control.
Under normal power operation, the emergency load will
track operation to the load tied to the yellow lead (load 1).
When normal power fails, the emergency relay will close
and the load will be forced on to full brightness.
Greengate
All provided wiring leads
N
ote:
are #14 AWG wiring.
Wire connections should
be rated suitable for the
wire size employed.
6
5
4
3
2
1
Dimmer 3
-
Dimmer 2
-
Dimmer 1
-
+
+
+
0-10V Dimming
9850-000366-04 page 4
October 2021