Greengate
Sample Placement Diagram
(For Example Purposes Only)
Daylight
Sensor
GPCS
Greengate
Patient
Control
Station
GG37P
The RC3DEHC is a healthcare based room solution that
simplifies design, installation and energy management
strategies for the patient room. The controller connects to
wallstations and a daylight sensor with provided Click & Go
QuickConnect cables, and easily integrates with the Greengate
Patient Control Station with terminal block connections to
provided GG37P Receptacle cabling. The GG37P Receptacle
also contains connections for the nurse call and entertainment
system for easy integration. Control up to three switched and
three dimmed loads without the need for post-installation
programming.
This document shows installation details regarding the Room
Controller and accessory products.
Room Controller with Plastic Enclosure (Model RC3DEHC Shown)
Room Controller with Metal Enclosure (Model RC3DEHC-PL Shown)
9850-000366-04 page 3
October 2021
Patient
General
Exam
Reading
Raise
Lower
Wallstation
All Off
Patient
Wallstation
General
Exam
Reading
All Off
Room Controller
(Above Ceiling
Over Headwall)
Specifications
Input/Output Voltage
Maximim Combined Load: 20A
Ballast
Incandescent
Motor Load
Emergency Output: (RC3DE only)
Ballast
Incandescent
Class 2 Dimming Output
Operating Environment
Mounting
Mount the room controller above the ceiling over the headwall
of the room being controlled.
Connect any necessary line and low voltage conduit directly to
the Room Controller.
Line Voltage
White
Red
Black
Green
-
A/V
+
Mode
-
Demand
+
Response
-
Alert
+
Mode
-
Time
+
Clock
Energy Options DIP Switch
Demand Response
Occupancy
1
2
Default 10%
Occ
20%
Vac (default)
30%
40%
0-10V Dimming Outputs
-
+
+
Dimmer 3
Dimmer 2
EmergencyLine
Voltage(RC3DE &
RC3DEHC only)
CAUTION
Bonding between conduit connections is not automatic and
must be provided as part of the installation.
Failure to install the Room Controller in the suggested loca-
tion above the entry door may lead to provided QuickConnect
cabling being too short to reach the intended accessory loca-
tions.
White
Red
Black
Green
-
A/V
+
Mode
-
Demand
+
Response
-
Alert
+
Mode
-
Time
+
Clock
Energy Options DIP Switch
Demand Response
Occupancy
1 2
Default 10%
Occ
20%
Vac (default)
30%
40%
0-10V Dimming Outputs
-
+
+
Dimmer 3
Dimmer 2
Room Controller for Healthcare
120/277 VAC 50/60Hz
20A
15A
1 HP @ 120 VAC
3A
3A
0-10 VDC, sinks up to 100mA
per output for control of up to 50
compatible ballasts/drivers.
32° F to 104° F (0° to 40° C)
For indoor use only.
Low Voltage
(Class 2)
6
Switchpack
Receptacle
BMS/Out
5
Sensors
Sensors
Slider
Station
4
Wallstations
3
2
1
Not Used
3
4
-
-
+
Dimmer 1
Dimmer 3
-
Dimmer 2
-
Dimmer 1
-
+
+
+
0-10V Dimming
6
Switchpack
Receptacle
BMS/Out
5
Sensors
Sensors
Slider
Station
4
Wallstations
3
2
1
Not Used
3
4
-
-
+
Dimmer 1
Dimmer 3
-
Dimmer 2
-
Dimmer 1
-
+
+
+
0-10V Dimming
www.cooperlighting.com