ENGLISH
1. Mounting the AMES module on AMV
323/423/523
A) Mount AMV motor on valve (fig. 1.1).
B) Remove lid from AMV motor (fig. 1.2).
C) Fit staybolts supplied with the AMES
module (fig. 1.3). If replacing a
module, the staybolts must also be
replaced.
D) If the AMES module is to be set up
using mains voltage, follow the
instructions in section 6: Automatic
setting up of AMES module .
E) Mount the AMES module in the motor
by pushing it half in over the
staybolts. Connect module leads in
motor terminal board (fig. 1.4) and
then push module fully into place.
Note: Before connecting the control
signal from the regulator to the AMES
24 V module, mains voltage must be
connected correctly as described in
section 5. Mains voltage.
2. Fuse (230 V~ only)
A) The fuse can be removed/replaced
by turning the fuse holder in the
direction of the arrow (figs. 2.1 and
2.2).
3. Function switch setting
Fig. 3.1 (U
= 0 -10 V, factory setting)
st
The AMV motor spindle travels upwards
on rising control voltage.
Fig. 3.2 (U
= 0 - 10 V)
st
The AMV motor spindle travels
downwards on falling control voltage.
Fig. 3.3 (U
= 0 - 5 V)
st
The AMV motor spindle travels upwards
on rising control voltage.
Fig. 3.4 (U
= 0 - 5 V)
st
The AMV motor spindle travels
downwards on rising control voltage.
Fig. 3.5 (U
= 5 - 10 V)
st
The AMV motor spindle travels upwards
on rising control voltage.
Fig. 3.6 (U
= 5 - 10 V)
st
The AMV motor spindle travels
downwards on rising control voltage.
Fig. 3.7 (U
= 0 - 20 mA)
st
The AMV motor spindle travels upwards
on rising control current.
Fig. 3.8 (U
= 0 - 20 mA)
st
The AMV motor spindle travels
downwards on rising control current.
4. Control voltage
Normal operation
The control signal from the regulator
must be connected to terminals 12 and
41 (U
2) on the AMES module (fig. 4.1)
st
Operation with on/off override
The control signal from the regulator
must be connected to terminals 12 and
41 (U
2) on the AMES module. The
st
override signal (e.g. from a clock or frost
thermostat) must be connected to
terminals 12 and 40 (U
1) (fig. 4.1).
st
Always use the contact set that has
low contact resistance.
BC-HM
6. Valve travel setting ("Stroke" set)
in the AMES module memory
Manual setting of AMES module
(Normal when adjusting motor valves
individually).
- Approx. 5 s after mains voltage is
connected, the red LED (by the
function switch) lights up (fig. 6.1).
- Press in the "Stroke" set button with a
screwdriver (fig. 6.1).
- The LED will flash while the motor
runs through a close/open cycle.
- When the valve travel has been
registered in the AMES module
memory, the LED again lights up
constantly and manual setting is
complete.
Automatic setting of AMES module
(Normal when setting several motor
valves at same time).
- Before mounting the AMES module,
clip the jumper on its underside
(fig. 6.2). (Note: it is still possible to
set the AMES module manually after
the jumper has been clipped).
- Switch on mains voltage until the red
LED (by the function switch) lights up
constantly.
- Switch off mains voltage for a
minimum of 6 s. (LED goes out).
- Switch on mains voltage for between
1 and 5 s. (The LED should remain
out).
- Switch off mains voltage for a
minimum of 6 s.
- Switch on mains voltage. The LED
will flash and the AMES module starts
automatic setting.
- When automatic setting is registered
in the AMES module memory, the
LED lights up again constantly and
automatic setting is complete.
Note: When the jumper is clipped, the
AMES module opens and closes the
valve completely, both in connection
with automatic setting and with possible
current failure during operation.
Therefore BE CAREFUL - there is a risk
of scalding when e.g. an AMES module
with clipped jumper is used for
regulating service hot water.
EI.94.E4.5Y © Danfoss 01/99
DEUTSCH
1. Montage des AMES Moduls im
AMV 323/423/523
A) AMV-Motor auf das Ventil montieren
(Abb. 1.1)
B) Den Deckel vom AMV-Motor
entfernen (Abb. 1.2)
C) Die mit dem AMES Modul gelieferten
Stehbolzen montieren (Abb. 1.3). Bei
einem eventuellen Austausch eines
Moduls sind die Stehbolzen ebenfalls
auszutauschen.
D) Erfolgt die Einstellung des AMES
Modul über die Netzspannung, ist
Abschnitt 6, Automatisches Einstellen
des AMES Moduls , zu befolgen.
E) Den AMES Modul in den Motor
einbauen, indem er vorerst halbwegs
über die Stehbolzen geschoben wird.
Die Leitungen des Moduls an die
Klemmenreihe des Motors
anschließen (Abb. 1.4) und dann das
Modul ganz auf Platz einschieben.
NB: Vor Anschluß des
Reglersteuersignals am AMES 24 V
Modul muß die Netzspannung
korrekt, wie in Abschnitt 5.
„Netzspannung" beschrieben,
angeschlossen sein.
2. Sicherung (nur 230V~)
A) Die Sicherung kann ausgewechselt
werden, indem der Sicherungshalters
in Pfeilrichtung gedreht wird (Abb. 2.1
und 2.2).
3. Einstellung des Funktionsschalters
Abb. 3.1 (U
= 0 - 10 V, Werks-
st
einstellung)
Die Spindel des AMV Motors bewegt
sich bei steigender Steuerspannung
aufwärts.
Abb. 3.2 (U
= 0 - 10 V)
st
Die Spindel des AMV Motors bewegt
sich bei steigender Steuerspannung
abwärts.
Abb. 3.3 (U
= 0 - 5 V)
st
Die Spindel des AMV Motors bewegt
sich bei steigender Steuerspannung
aufwärts.
Abb. 3.4 (U
= 0 - 5 V)
st
Die Spindel des AMV Motors bewegt
sich bei steigender Steuerspannung
abwärts.
Abb. 3.5 (U
= 5 - 10 V)
st
Die Spindel des AMV Motors bewegt
sich bei steigender Steuerspannung
aufwärts.
Abb. 3.6 (U
= 5 - 10 V)
st
Die Spindel des AMV Motors bewegt
sich bei steigender Steuerspannung
abwärts.
Abb. 3.7 (U
= 0 - 20 mA)
st
Die Spindel des AMV Motors bewegt
sich bei steigendem Steuerstrom
aufwärts.
Abb. 3.8 (U
= 0 - 20 mA)
st
Die Spindel des AMV Motors bewegt
sich bei steigendem Steuerstrom
abwärts.
4. Steuerspannung
Normalbetrieb
Das Steuersignal vom Regler wird an
3