Descargar Imprimir esta página

Lenze E94APNE04 Serie Instrucciones Para El Montaje página 30

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

Overview
Standard device 
Pos.
Description
X11
24 V supply
X12
4 digital outputs
1 digital input
Nameplate, retractable
Setting of mains voltage/brake chopper threshold
Upper cap
The LED display enables fast indication of several operating states.
LED
Labelling
-
OVERHEAT
MAINS
BRCHOP FAIL
24 V
BRCHOP ON
SSP94LED21
Pos.
Symbol
Installation backplane 
Pos.
Description
X111
Mains (supply from the top, e.g. through top-mounted filter)
DC-bus voltage (compatible to 9300 series)
X112
Mains (supply from the bottom, e.g. through side-mounted filter)
External brake resistor
X109
DC busbar +
X110
DC busbar -
EMC shield clamp
© 2006 Lenze Drive Systems GmbH, Hans-Lenze-Straße 1, D-31855 Aerzen
No part of this documentation may be reproduced or made accessible to third parties without written consent by Lenze Drive
Systems GmbH.
All information given in this documentation has been selected carefully and complies with the hardware and software described.
Nevertheless, deviations cannot be ruled out. We do not take any responsibility or liability for damages which might possibly occur.
Necessary corrections will be included in subsequent editions.
30
All manuals and user guides at all-guides.com
Colour
Description
-
-
Red
Overtemperature
Green
Mains voltage OK
Red
Short circuit on brake chopper
Green
24 V supply voltage OK
Yellow
Brake chopper active
Description
Long discharge time: All power terminals carry hazardous voltages for at
least 3 minutes after mains disconnection!
High discharge current: Fixed installation and PE connection to EN 61800-5-1
required!
Electrostatic sensitive devices: Before working on the device, personnel must
ensure that they are free of electrostatic charge!
Direct connection of axis
modules
EDK94PNE36 DE/EN/FR/ES/IT 2.0

Publicidad