Technical data
General data and operating conditions
3
Technical data
3.1
General data and operating conditions
Supply system data
Supply forms
Noise emission
Noise immunity
Standards
Conformity
Approval
Protection
Enclosure
Insulation resistance
Discharge current
Environmental conditions
Climate
Storage
Transport
Operation
Site altitude
Pollution
Vibration resistance
38
All manuals and user guides at all-guides.com
With earthed neutral Unrestricted use
IT systems
Observe instructions about special measures!
EN 61800-3
Cable-guided: cannot be specified because dependent on the
conditions present in the interconnected system
Radiation: category C3
EN 61800-3
Category C3
CE
Low-Voltage Directive (73/23/EEC)
UL 508C
Power Conversion Equipment (file no. 132659)
EN 60529
IP 20
NEMA 250
Protection against contact to
type 1
EN 61800-5-1
Overvoltage category III
Derating at and above 2000 m: overvoltage category II
EN 61800-5-1
> 3.5 mA
IEC/EN 60721-3-1
1K3 (-25 ... +60 °C)
IEC/EN 60721-3-2
2K3 (-25 ... +70 °C)
IEC/EN 60721-3-3
3K3 (-10 ... +55 °C)
Power derating at +45 ... +55 °C: 2.5 %/°C
0 ... 4000 m amsl
Power derating at 1000 ... 4000 m amsl: 5 %/1000 m
EN 61800-5-1
Pollution degree 2
Germanischer Lloyd
General conditions: acceleration resistant up to 0.7 g
Not in the wire range of
the terminals on the
motor side
Observe regulations and
safety instructions!
EDK94PNE36 DE/EN/FR/ES/IT 2.0