�4 | ��A ��� | Technical data
7.
Technical data
i
All the values given are referenced to a temperature
of +20 °C.
Insulation analysis
i
The specifications only apply in conjunction with the
remote sensor and the measurement leads contai-
ned in the scope of delivery.
i
Measurement starts at 0.00 MΩ for all ranges.
Range
Accuracy
1000 V
200 GΩ ± 3 % ± 2 positions ± 0.2 % per GΩ
500 V
100 GΩ ± 3 % ± 2 positions ± 0.4 % per GΩ
250 V
50 GΩ ± 3 % ± 2 positions ± 0.8 % per GΩ
100 V
20 GΩ ± 3 % ± 2 positions ± 2.0 % per GΩ
50 V
10 GΩ ± 3 % ± 2 positions ± 4.0 % per GΩ
�unction
�pecification
Analog
1 GΩ for full scale deflection
display range
Short-circuit
2 mA +0 % -50 %
current
Terminal
-0 % +20 % ±1 V (Ii <1 mA)
voltage
Test current level
1 mA for minimum insulation continuity
under load
value according to specification as per
BS7671, HD384 and IEC364, EN 61152-2,
2 mA maximum
EN 61557
0.10 MΩ to 1.00 GΩ
operating range
Leakage current
10 μA to 2000 μA
measurement ran-
ge
Leakage current
10 % ±3 positions
Voltage display
3 % ±3 positions ±0.5 % of rated voltage
Polarisation
Ratio of 10 minutes to 1 minute
index (PI)
Dielectric
Ratio of 60 s to 30 s
absorption ratio
(DAR)
Continuity measurement
�unction
�pecification
EN 61557
0.01 Ω to 99.9 Ω
operating range
(0 to 100 Ω on analog scale)
Accuracy
±2 % ±2 positions (0 to 100 Ω)
Voltage in
5 V ± 1 V
open circuit:
Test current
205 mA (±5 mA) (0.01 Ω to 9.99 Ω)
20 mA (±1 mA) (10.0 Ω to 99.9 Ω)
Zero adjustment
Usually 0.10 Ω
at remote
sensor tips
Zero adjustment
Up to 9.99 Ω
of line resistance
Buzzer
Variable limit: 1 Ω, 2 Ω, 5 Ω, 10 Ω, 20 Ω
|
1 689 989 102
2011-04-26
Resistance measurement
�unction
�pecification
EN 61557
0.01 kΩ to 1000 kΩ
operating range
(0 to 1 MΩ on analog scale)
Accuracy
±5 % ±2 positions
Voltage in open
5 V ± 1 V
circuit
Short-circuit
20 μA ±5 μA
current
Voltage measurement
R
0 to 600 V DC ± 2 % ± 2 positions
R
10 mV to 600 V TRMS sinusoidal (40–400 Hz) ±2 % ±2
positions
R
0 to 1000 V on the analog scale
R
Non-specified input level 0 – 10 mV (40 – 400 Hz)
R
Additional specifications apply to non-sinusoidal
curves:
$
±3 % ±2 positions / 101 mV – 600 V TRMS and
$
±8 % ±2 positions / 10 mV – 100 mV TRMS
�tandard voltmeter
R
Operates at >25 V AC or DC in any range except OFF
R
Frequency:
40 – 450 Hz (40 Hz – 99.9 Hz) ±0.5 % ± 1 position
(100 Hz to 450 Hz)
Capacitance measurement
�unction
�pecification
Measuring range
100 pF to 10 μF
Accuracy
±5.0 % ± 2 positions
�torage of measurement results
�unction
�pecification
Capacity
> 1000 test results
Download
Bluetooth wireless
Bluetooth class
I/II
Workshop environment
in the open space:
Class 1
30 m
Class 2
5 m
i
The Bluetooth class can only be set using the
CompacSoft[plus] software.
Power supply
Five 1.5 V cells of type IEC LR6 (AA, MN1500, HP7, AM3
R6HP) alkaline or rechargeable NiMH.
Battery service life
2200 insulation tests with a duty cycle of 5 s ON and
55 s OFF at 1000 V and 1 MΩ