Requirements for on-site installation
Inlet water connection
Location
Construction
Inlet water temperature
Water quality
Water hardness
Water flow pressure
Max. inlet pressure
(back pressure)
Flow rate
Limit values for the raw water with PTD 701 AE RO / PTD 702 AE RO
Electrical conductivity
(at 25°C)
Chlorine
Silicate (as SiO
)
2
Waste water connection
Location
Construction
Electrical connection
Location
Construction
Fuse protection
Mains cable
Subject to technical alterations
approx. 400 mm above finished floor; next to the machine
Isolation valve with G ¾" external thread
Standard
PTD 701 AE RO,
PTD 702 AE RO
Microbiologically, fresh water must be of drinking water quality
Standard
PTD 701 AE RO,
PTD 702 AE RO
Standard
PTD 701 AE RO,
PTD 702 AE RO
1000 kPa (10,0 bar)
min. 4 l/min
< 1200 μS/cm
< 0,2 mg/l
< 30 mg/l
approx. 600 mm above finished floor; next to the machine
Trap on-site
approx. 300 mm above finished floor; next to the machine
Wall outlet for machines without power plug
We recommend installing a mains isolation switch with all-pole disconnection from the mains supply
in the case of a fixed connection (without plug) so as to be able to ensure the absence of voltage
during installation and maintenance.
Mains socket for machines with power plug
If a residual current circuit breaker is present on-site, we recommend installing a Class B all-current
sensitive residual current circuit breaker.
Depends on the total connected load of the machine (see separate table)
3000 mm long
2
Cross section: 2.5 mm
(220V-240VN~/380V-415V3N~,50Hz)
2
Cross section: 4.0 mm
(230V3~/380V - 415V3N~,50Hz); country variant Belgium, Norway
Connection according to operating instructions if not connected
max. 60°C
max. 35°C
Machines without integrated
softener
≤ 3 °dH (3.8 °e / 5.34 °TH / 0.54
mmol/l)
Recommended, to prevent ware-
washer from scaling up.
≤ 35 °dH (43.9 °e / 62.3 °TH /
6.3 mmol/l)
100 kPa (1,0 bar)
140 kPa (1,4 bar)
|
|
11208062/01; 2023-03
Machines with integrated
softener
≤ 31 °dH (37.6 °e /
53.4 °TH / 5.35 mmol/l)
-
12