8.4.5 Common Heating/Cooling household in combination with Individual DHW production
This installation is suitable when there are different demands of
DHW applications:
-
Different DHW setting temperature
-
Different DHW usage patterns
-
Variety of DHW volume required
DHW production or Space Heating/Cooling production
is simultaneously. This means that YUTAKI CASCADE
CONTROLLER can operate for Space Heating/Cooling
application and each configured Sub can operate for DHW when
needed. Each Circuit 2 will continue working by using Mixing kit
YUTAKI
1
E.HEATER
3WV DHW
TDHW
YUTAKI
2
E.HEATER
3WV DHW
TDHW
YUTAKI
n
UP to 8
Example for illustrative purpose
Mainly configuration
Configuration in YUTAKI CASCADE CONTROLLER Side:
1 Circuit 1: Enabled at gradient/point/fixed temperature (thermostat option) (Direct Circuit)
2 Circuit 2: Enabled at gradient/point/fixed temperature (thermostat option) (Mixing Circuit)
3 DHW: Disabled
4 Cascade Configuration Menu (Example in case that 6 modules are connected):
Example 1
Cascade configuration menu
Status
Refrigerant cycle address
Indoor unit address
Individual DHW
Status
Type
Configuration in YUTAKI Sub Side (Each Sub it have similar configuration):
1 Central control: Cascade Mode: Enabled
2 Circuit 1:Enabled at Fixed setting temperature (without room
thermostat)
3 Circuit 2: Disabled
4 DHW: Enabled (By central controller automatically)
15
PMML0581 rev.1 - 02/2023 - 1000011627
DHW
H-LINK
DHW
TWO3
C1
BUFFER TANK
Module 1
Module 2
Module 3
Enabled
Enabled
Enabled
0
1
0
0
-
-
Enabled
Enabled
Disabled
Main
Main
and accumulate water into C1 Buffer tank.
In this scenario, YUTAKI CASCADE CONTROLLER manage
both Space Heating/Cooling household and YUTAKI DHW
Production:
•
C1 and C2 management is performed by means of YUTAKI
CASCADE CONTROLLER.
•
C1 and C2 can have wired/wireless/none thermostats or any
combination option.
•
Installer shall determine proper usage of collector systems.
YCC
YCC
ATW-YCC-03
RECEIVER
ATW- RTU-07/08
Module 4
Module 5
Enabled
Enabled
2
3
4
0
0
0
-
-
-
Disabled
Disabled
-
-
-
5 Additional configuration:
a. Each unit need to assign Refrigerant address
(0/1/2/3/4/5/6/7) in accordance with YUTAKI CASCADE
CONTROLLER modules configuration
b. The water pump in each Sub unit can be set to Standard
(continuous operation) or Economic mode (operation
only in case that there is operation demand from the
CASCADE CONTROLLER or if the Sub unit has its own
tank and is in demand ON conditions).
CIRCUIT 1
CIRCUIT 1
SPACE HEATING/COOLING
SPACE HEATING/COOLING
PC-ARFH2E
ATW- RTU-07/08
CIRCUIT 2
CIRCUIT 2
SPACE HEATING/COOLING
SPACE HEATING/COOLING
PC-ARFH2E
ATW- RTU-06/09
Module 6
Module 7
Module 8
Enabled
Disabled
Disabled
5
6
0
0
-
-
Disabled
Disabled
Disabled
-
-
Or
Or
7
0
-
-