ELECTRICAL AND CONTROL SETTINGS

DSW1: Model setting
Setting is required.
Set DSW1 according to the Sub units model
YUTAKI S (*)
YUTAKI S COMBI (*)
?
N O T E
(*) In case of installing the "Cooling kit" accessory, set the pin 4 of DSW1 to ON in order to enable the cooling operation in the Sub units and in the
YUTAKI CASCADE CONTROLLER.

DSW2: Model capacity setting
Setting is required in order to match with the model of the YUTAKI Sub installed.
Factory setting
4.0 HP

DSW3: Additional setting 1
Setting before shipment
1-step heater for 3-phase unit

DSW4: Additional setting 2
Setting before shipment
Heater forced OFF
Unit and installation pipes antifreeze protection
Standard / ECO water pump operation
Electric heater or boiler emergency mode
DHW tank's heater operation
!
C A U T I O N
Never turn all DSW4 dip switch pins ON. If this happens, the software of the unit will be removed.
Never activate "Heater Forced OFF" and "Electric heater or boiler emergency mode" at the same time.
22
PMML0581 rev.1 - 02/2023 - 1000011627