Evaporative Cooling System
Evaporative Media Document
Proper design, installation, and maintenance are critical in maximizing the life of your
new cool cell pads. Please follow the below recommendations.
DESIGN
A MAXIMUM permissible airflow velocity of 400 feet per minute measured at the pad should be strictly adhered
to. Velocities exceeding 400 feet per minute can lead to pad warpage and the decrease of pad life.
INSTALLATION
The orientation of each cool cell pad is marked on the side of each cool cell pad. Along with the vertical
orientation it is critical that the black edge guard faces the exterior of the building.
During installation the water level and setting of the float valve should be inspected. The water level should be
roughly 1 inch below the trough cover. If level is incorrect adjust float.
COOL CELL PADS SHOULD NEVER BE SUBJECTED TO STANDING WATER AT THE BASE OF THE
During normal operation the cool cell pads should be allowed to fully dry daily. After turning off the cool cell
pump allow tunnel fans to run for additional 30 minutes to complete the drying process.
MAINTENANCE
During operation the pH of the cool cell system should be between 6 and 8.5. pH should be monitored (at least
initially) on a weekly basis to determine schedule for flushing the system. Once the pH reaches 8.5, the system
should be allowed to drain then refilled with fresh water. The monitoring of pH and routine flushing of the system
helps to reduce mineral build up in the pads as well as the water reservoirs.
Below are min/max levels used to qualify acceptable water quality.
Cleaning of cool cell pads can help to extend the pad life. The following is a list of recommended algaecides and
descalers that can be used to clean the systems.
AT NO POINT SHOULD CHLORINE (BLEACH) EVER BE USED TO CLEAN COOL CELL PADS
STRICTLY FOLLOW LABEL DIRECTIONS EXACTLY WHEN USING CLEANING CHEMICALS
Approved Algaecides
Synergize Non
Foaming
Virocid
CWT
The list above is recommended algaecides and descalers. Please contact your local Hog Slat
Hog Slat Inc. Newton Grove, NC USA February 2019
NEVER CLEAN PADS WITH PRESSURE WASHER
Part Number
24494
BV061
CWTUN1903
representative for a complete list of approved chemicals.
PADS!
Approved Descalers
Aqua Max XL
Cool N Kleen
DeVere Power Descaler
Part Number
79105
I52996
MPD8/MPD100
Part Number: HSMANUAL-148
HSART-519
Market: Hog & Poultry
21