ACCESSORIES
» WM-UH-ECM-NTC (code 9008136)
Kit for room air probe remote control.
The NTC probe is delivered mounted inside a
watertight plastic box.
The NTC probe must be connected to the WM-
UH-ECM controller and allows the detection of
the room temperature.
Installation procedure:
1.
Remove the upper cover of the WM-UH-
ECM control to access the electronic board.
2.
Disconnect the air probe B1 from the con-
nector T1 of the electronic board.
3.
On the terminal board inside the control a
T1
REMOVE
wiring harness with connector is already
installed and will be used to support the
installation of the remote probe: connect
the wiring connector to the connector T1
of the board.
4.
Connect the NTC remote probe to termi-
nal "T1" of the WM-UH-ECM control termi-
nal board, using a LiYY signal cable with
2x0.35 mm² section.
5.
Restore the control panel.
36
CONNECT
T1
T1
T1