to start the let-by test procedure.
Wait 1 minute instrument countdown for leak measurement.
Print the report. Press:
B. Test B - two minute tightness test
Select and confirm the "
Change and confirm test type to "Test B" for two minute let-by test.
Press the "ZERO" function (F1) to zeroing the pressure sensor.
Connect the pressure input
Connect the kit to the gas network.
plugs for connecting.
Open the valve on "T" connector.
Pressurize the network at the testing pressure.
Close the valve on "T" connector.
Select the "START" option pressing:
Press
to start the let-by test procedure.
Wait 1 minute instrument countdown for network stabilization.
Wait 2 minute instrument countdown for leak measurement.
Print the report.
The leak test B countdowns are programmable from keyboard. Read the
Technical Specifications
This product is fully compliant with part 2 and part 3 of EN 50379
Type: 2 or 3 cells hand-held flue gas analyser/Boiler tuning unit.
Internal Printer: Impact type 24 columns
Autozero: Automatic 60 sec. procedure at startup for sensor calibration
and instrument self diagnosis.
Printer power supply: using the analyser battery pack.
Power supply: High capacity Li-ion rechargeable battery pack / external
battery charger (90..264V 50/60Hz).
Charging time : approx 3h at 90% with instrument off.
Battery life: 7h continuous operation printer and back-light off).
Display: Large (40x56 mm), monocrome, graphic LCD display with
automatic back-light device.
Fuel types: Up to 10 totally programmable (the standard set depends by
the national local regulation).
Data memory: up to 250 complete analysis data structured by Tags.
Serial interface: USB standard interface.
Battery storage temperature: 0 to 35°C
Working temperature: -5°C to +45 °C (up to 50°C for short time)
Storage temperature: –20 to +50°C (3 months maximum at temperatures
exceeding the operational limits).
Dimensions: 115x70x300 mm
Weight: Nett. 1.1 kg battery and printer included
Parameter
O
2
CO
H compensated
2
CO diluted
NO
Tair
Tgas
Pressure
Draft
All emission measurements can be displayed with reference to a programmable O value.
Accuracy limits are stated as % of reading. An additional ±1 digit error has to be considered.
The stated pressure relative accuracy is valid only after the zero procedure.
Measuring reading can be directly converted from °C to °F, ppm to mg/Nm and from hPa to
mmH O, mbar, inH O.
2
8
Test type
P1
Press:
Instruction manual included in the CD-ROM.
Range
0 - 25%
0 - 8000ppm
0.8 - 10%
0 - 4000ppm
-10 - 100°C
0 - 1000°C
0 - 200 mbar
±40.00 hPa
2
" option.
to the leak test kit (cat. 26028).
If required, use the rubber blanking
IMPORTANT
Resolution
0.1%
1ppm
0.05%
1ppm
1°C
1°C
0.1mbar
0.01 hPa
Accuracy
±0.1% vol.
±10ppm <300ppm
±4%rdg up to 2000ppm
±10%rdg elsewhere
±5ppm <125ppm
±4%rdg up to 4000ppm
±(0.2% + 0.15°C)
±(0.3% + 0.3°C)
±0.5mbar <50 mbar
±1%rdg >50 mbar
±0.03 hPa < 300 Pa
±1% rdg. > 300 Pa
2