30/36
Resetting user settings
Button / display
nff
12.2 Changing the collision detection sensitivity (overcurrent)
Button / display
or
P08
Button [1]
or
Button [1]
13 Resetting user settings
The following settings are reset:
• Storage location 1 to 4
• Upper stroke limitation
• Lower stroke limitation
• Collision recognition
• Unit of the display
• Setting the height of the application
• Safety area
Button / display
or
P12
Button [1]
P30
Button [1]
Button [2]
Bosch Rexroth AG, MPS: Steuergerät, 3 842 564 712/2022-06
Instruction / explanation
n = lifting module at port n= 1,2,3
ff = error no. "F"
e.g. 222 = lifting module at port 2 of the control unit has an error at the
position measurement system F22 -> service / replace
Instructions
Push shortly four times in a row
A tone sequence resounds and "PXX" is shown in the display (A)
Push to select a menu item
Collision detection sensitivity
Push to select menu item
The display shows the current sensitivity:
2: Factory setting, highest sensitivity
3: Medium sensitivity
4: Lowest sensitivity
Select the desired setting
Push to confi rm menu item
Instructions
Push shortly four times in a row
A tone sequence resounds and "PXX" is shown in the display (A)
Push to select a menu item
Service menu
Push to select menu item
Resetting user settings
Push to reset the values
Push to exit the menu
⇒
"2" max. sensitivity
⇒
cm
⇒
0 cm
⇒
25 mm