Change of lighting time of
filter sign
According to the installation condition, the lighting time
of the filter sign (Notification of filter cleaning) can be
changed.
Follow the basic operation procedure
(1 → 2 → 3 → 4 → 5 → 6 ).
3
• For the CODE No. in Procedure
, specify [01].
4
• For the SET DATA in Procedure
, select the
SET DATA of filter sign lighting time from the
following table.
SET DATA
Filter sign lighting time
0000
None
0001
150 H
0002
2500 H (Factory default)
0003
5000 H
0004
10000 H
To secure better effect of
heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator, etc. to circulate heat air
near the ceiling.
Follow the basic operation procedure
(1 → 2 → 3 → 4 → 5 → 6 ).
3
• For the CODE No. in Procedure
, specify [06].
4
• For the SET DATA in Procedure
, select the
SET DATA of shift value of detection temperature
to be set up from the table below.
SET DATA
Detection temperature shift value
0000
No shift
0001
1.8 °F (+1 °C)
3.6 °F (+2 °C)
0002
(Factory default)
0003
5.4 °F (+3 °C)
0004
7.2 °F (+4 °C)
0005
9.0 °F (+5 °C)
0006
10.8 °F (+6 °C)
37-EN
– 19 –
Changing the wind direction
Up / down direction: Horizontal louvers
* Display while swinging
Cancelling swing
* Display when swinging (up / down) is
cancelled "Fan", "Heat"
* Display when swinging (up / down) is
cancelled "Cool", "Dry"
1
Press [
] and [
] to switch to the "Wind
direction" screen (horizontal louvers)
2
Press [
] and [
] to select wind
direction
Operation mode
Operation mode
(1), (2), (3), (4), (5),
Heat, Fan, Auto (Heat)
Swing
Cool, Dry, Auto (Cool)
(1), (2), (3), Swing
1
During swing operation, press [
] and [
to switch to the "Wind direction" screen
2
Press [
] or [
]
The louvers stop at the position when [
[
] is pressed.
When [
] is pressed in the display when swing
was cancelled, the louvres go to wind direction
position (1), when [
] is pressed, the louvers
go to position (3) during "Cool" or "Dry" operation,
and go to position (5) during "Fan" or "Heat"
operation.
]
] or