Mapa de las Pantallas del OID (continuación)
101 SYSTEM SETPOINTS
Engine Start
Pressure
[100.0]psi
0-999.9
102 SYSTEM SETPOINTS
Engine Stop
Pressure
[110.0]psi
0-999.9
103 SYSTEM SETPOINTS
Engine Start Delay
Time
[ 1] seconds
1-999
104 SYSTEM SETPOINTS
Engine Automatic
Stop Enabled
[Yes]
105 SYSTEM SETPOINTS
Engine Minimum
Run Time
[30]minutes
30-99
106 SYSTEM SETPOINTS
Automatic Weekly
Engine Test Run
[Yes]
107 SYSTEM SETPOINTS
Auto Weekly Engine
Test Day Of The Week
[Mon]
108 SYSTEM SETPOINTS
Auto Weekly Engine
Test Start Time
[10:00:00]
109 SYSTEM SETPOINTS
Auto Weekly Test
Length Of Run Time
[30] minutes
30-99
110 SYSTEM SETPOINTS
Auto Weekly Test
Oil/Water Shutdown
[No]
111 SYSTEM SETPOINTS
Power Failure Engine
Startup
[No]
112 SYSTEM SETPOINTS
Power Failure Engine
Start Delay Time
[ 1] minutes
0-500
113 SYSTEM SETPOINTS
Pressure Transducer
Failure Engine Start
[Yes]
114 SYSTEM SETPOINTS
Surge Control Valve
Open/Close Control
[No ]
115 SYSTEM SETPOINTS
Surge Control Valve
Delay Time
[ 15] seconds
0-999
116 SYSTEM SETPOINTS
Shutdown On Low
Intake Pressure/Lvl
[No ]
117 SYSTEM SETPOINTS
Shutdown On Low
Intake Trip Time
[ 20]seconds
0-999
118 SYSTEM SETPOINTS
Low Intake Shutdown
Auto Reset
[Yes]
119 SYSTEM SETPOINTS
Low Intake Shutdown
Auto Reset Time
[ 20]seconds
0-999
120 SYSTEM SETPOINTS
Pressure Switch
Engine Start
[No ]
121 SYSTEM SETPOINTS
Deluge Valve
Engine Start
[Yes]
122 SYSTEM SETPOINTS
High System Pressure
Alarm
[175.0]psi
999.9
1
CONFIG
1) SYSTEM SETPOINTS
2) USER PREFERENCES
3) TECH SCREENS
2
CONFIG
1) ANALOG SIGNALS
2) AUXILLIARY ALARMS
201 USER PREFERENCES
301
TECH SCREENS
Set System Real
SPECIAL: Engine
Time Clock
Minimum Run Time
[17:03:52]
[No ]
202 USER PREFERENCES
302
TECH SCREENS
Set System Date
SPECIAL: Engine
Minimum Run Time
[02/16/03]
[15]minutes
203 USER PREFERENCES
303
TECH SCREENS
Set System Day
Energized To Stop
Of The Week
Fuel Solenoid Time
[Sun]
[10]seconds
204 USER PREFERENCES
304
TECH SCREENS
Log System Pressure
Low Oil Pressure
Drop Events
Alarm Delay Time
[Yes]
[ 7]seconds
205 USER PREFERENCES
305
TECH SCREENS
Low Pressure Event
Nominal Battery
Trip Pressure
Voltage
[ 60.0]psi
0-999.9
[12]VDC
206 USER PREFERENCES
306
TECH SCREENS
Low Pressure Event
Battery Low Voltage
Reset Time
Alarm Trip Voltage
[15] seconds
0-20
[ 9.0]VDC
207 USER PREFERENCES
307
TECH SCREENS
Time Between
Battery Low Voltage
Pressure Log Samples
Alarm Trip Time
[ 15] seconds 15-999
[ 5]seconds
208 USER PREFERENCES
308
TECH SCREENS
Auto Print Each
Change Tech Password
Pressure Log Sample
[******]
[No ]
209 USER PREFERENCES
309
TECH SCREENS
Auto Print Each
Password Logout
Event Log Entry
Time
[No ]
[ 5] minutes
210 USER PREFERENCES
310
TECH SCREENS
Selective Range
System Commissioned
Printing
Date
[ 1] Before
1-99
[00/00/00]
211 USER PREFERENCES
311
TECH SCREENS
Selective Range
Expiration Time
Printing
For Test Settings
[ 1] After
1-99
[ 5]minutes
212 USER PREFERENCES
312
TECH SCREENS
LCD Back Light Mode
STARTUP TEST: Test
0=Always on
Settings Enabled
[No ]
[0]]
1=Power Save
213 USER PREFERENCES
313
TECH SCREENS
Language Select
STARTUP TEST: Engine
0=English, 1=Spanish
Minimum Run Time
[0]
[15]minutes
214 USER PREFERENCES
314
TECH SCREENS
Change User Password
FACTORY TEST: Test
Level 1
Settings Enabled
[****]
[No ]
215 USER PREFERENCES
315
TECH SCREENS
Save Aux alarms
FACTORY TEST: Engine
to SD memory card
Crank Time
[ No]
[15]seconds
216 USER PREFERENCES
316
TECH SCREENS
Load Aux alarms
FACTORY TEST: Engine
from SD memory card
Crank Rest Time
[No]
[15]seconds
317
TECH SCREENS
Alarm Log
Event Log
Pr. Log
File Name: Doc#586g-Spanish.doc
400 ANALOG SIGNALS
Analog Input 01
Slope:
[0.2135677]
401 ANALOG SIGNALS
Analog Input 01
Offset:
1-99
[- 75.6030]
402 ANALOG SIGNALS
Analog Input 1
651
Minimum Counts
0-99
[ 200]
410 ANALOG SIGNALS
Analog Input 02
Slope:
1-99
[0.0350000]
411 ANALOG SIGNALS
Analog Input 02
Offset:
10-99
[
0.0000]
412 ANALOG SIGNALS
Analog Input 2 1174
Minimum Counts
8-99
[
0]
420 ANALOG SIGNALS
Analog Input 03
Slope:
0-99
[0.0350000]
421 ANALOG SIGNALS
Analog Input 03
Offset:
[
0.0000]
422 ANALOG SIGNALS
Analog Input 3 1225
Minimum Counts
1-15
[
0]
ANALOG INPUT COUNTS
649 1176 1221
0
0
0
0
0
0
0
424 BATTERY 1
Constant A
xA^3 + xB^2 + xC + D
1-60
[ 0.0000]
425 BATTERY 1
Constant B
xA^3 + xB^2 + xC + D
[ 0.0000]
426 BATTERY 1
Constant C
xA^3 + xB^2 + xC + D
[ 0.004190]
1-99
427 BATTERY 1
Constant D
xA^3 + xB^2 + xC + D
[- 0.096642]
428 BATTERY 1
Volts per count
[1.0000000]
1-15
429 BATTERY 1
Minimum Amps
[
1.0]
1-15
430 BATTERY 2
1/10
Constant A
xA^3 + xB^2 + xC + D
1/1569
[ 0.0000]
1/25123
431 BATTERY 2
Constant B
xA^3 + xB^2 + xC + D
[ 0.0000]
432 BATTERY 2
Constant C
xA^3 + xB^2 + xC + D
[ 0.004190]
433 BATTERY 2
Constant D
xA^3 + xB^2 + xC + D
[- 0.096642]
434 BATTERY 2
Volts per count
[1.0000000]
435 BATTERY 2
Minimum Amps
[
1.0]
Page 13 of 33
501 AUX USER PROGRAM
AUX# 1
Enabled
[Yes]
502 AUX USER PROGRAM
AUX# 1
Input Number
[30]
0-53
503 AUX USER PROGRAM
AUX# 1
Input Contact Type
[NO ]
504 AUX USER PROGRAM
AUX# 1
Trip Time
[
0]sec
0-999
505 AUX USER PROGRAM
AUX# 1
Reset Time
[
0]sec
0-999
506 AUX USER PROGRAM
AUX# 1
Auto Reset Enabled
[Yes]
507 AUX USER PROGRAM
AUX# 1
Horn Enabled
[No ]
508 AUX USER PROGRAM
AUX# 1
Horn Silence
[No ]
509 AUX USER PROGRAM
AUX# 1
LED Number
[ 0]
0-24
510 AUX USER PROGRAM
AUX# 1
Output1 Number
[ 0]
0-19
511 AUX USER PROGRAM
AUX# 1
Output2 Number
[ 0]
0-19
512 AUX USER PROGRAM
AUX# 1
Output3 Number
[ 0]
0-19
513 AUX USER PROGRAM
AUX# 1
Record In Event Log
[No ]
514 AUX USER PROGRAM
AUX# 1
Text Message Number
[ 0]
0-27