DIAGNOSTICS
Inputs/Outputs
This function enables the display of the operating status of all inputs and outputs present on the control unit. The functions of
the inputs and outputs are described in Table 5.
PARAMETER
Diagnosis 1 - IN
RADIO INPUTS (On / Off):
Channel 1
Channel 2
Channel 3
Channel 4
SERIAL RADIO INPUTS
BOARD KEYS:
no. 1
no. 2
no. 3
BINPUT STATUS:
inp 1
inp 2
inp 3
inp halt
HALT CONFIGURATION
MANOEUVRE THRESHOLD
LAST 8 MANOEUVRES
AUTOMATIC OPENING
Diagnosis 1 - OUT
GENERAL DATA
Stand-by
POWER SUPPLY
MEMORY ERRORS
Functions
Bluebus
Positions
TABLE 5: input/output DIAGNOSTICS
DESCRIPTION
Indicates when radio receiver channel 1 is active.
Indicates when radio receiver channel 2 is active.
Indicates when radio receiver channel 3 is active.
Indicates when radio receiver channel 4 is active.
Indicates when the control unit receives a serial command via BusT4
from a radio receiver; these commands range from minimum 1 to
maximum 15.
Indicates when key 1 is pressed (= OPEN) on the control unit.
Indicates when key 2 is pressed (= STOP) on the control unit.
Indicates when key 3 is pressed (= CLOSE) on the control unit.
Indicates when input 1 is active.
Indicates when input 2 is active.
Indicates when input 3 is active.
Indicates when the halt input is active.
Indicates the type of connection on the halt terminal. Connection
types are: not configured; NC; NO; 1 8K2 resistive edge; 2 8K2 resis-
tive edges; out of range.
Indicates the operating status of the manoeuvre limiter, expressed in
levels:
Level 1: OK
Level 2: THRESHOLD 1; the manoeuvre is started with a 2 second
delay
Level 3: THRESHOLD 2; the manoeuvre is started with a 5 second
delay
Level 4: MOTOR ALARM; the manoeuvre is only enabled with the
hold-to-run control
Indicates any malfunctions occurring during normal operation of the
application, showing the last 8 manoeuvres completed.
Indicates if this function is active.
Indicates when the automation is in the standby status.
Indicates the type of electrical mains used by the automation: electric
mains (120/230 Vac) or buffer battery (24 Vdc)
Indicates whether there is an error in the memorised data regarding
the functions programmable with Oview.
Indicates whether there is an error in the memorised data regarding
the configuration of the devices connected to the bluebus input.
Indicates whether there is an error in the memorised data regarding
positions.