Instalación eléctrica
7
Instalación conforme a UL
DC 450 V – 800 V circuits
Manufacturer
Description
Siba
SQB 1 DIN 110
Manufacturer
Description
Siba
10 × 38 mm
7.9.4
Ambient temperature
7.9.5
Environmental conditions
56
Instrucciones de funcionamiento – Módulo de freno seguro SBM para montaje en el armario de conexiones
If the AC fuse used is not covered according to section "AC 380 – 480 V / 500 V devi-
ces", or if a DC fuse of the supply line is necessary due to other requirements, the fo-
llowing fuses must be used:
•
SCCR: 65 kA / 800 V
Order code
SEW order code
2071332.50
-
•
SCCR: 30 kA / 800 V
Order code
SEW order code
5019906.15
19051603
The units are suitable for a maximum surrounding air temperature of max. 60 °C.
The units are for use in pollution degree 2 environments.
Ratings
DC 900 V; 50 A; 100 kA
Ratings
DC 1000 V; 15 A; 30 kA
Class
UL
aR
248 – 13
Class
UL
gR