Fig. 12: Pressure regulator, two-channel and single-channel
12
Pressure gauge connection for con-
nection 2
14
Blanking plug
16
Lock nut
18
Adjustment screw for connection 4
7.3 Shutoff module: Blocking the working pressure
The shutoff module and the air circuit should be tested monthly to en-
sure they function correctly.
7.3.1 Manually operated shutoff module
To block the operating line:
1. Use a screwdriver to turn the lock (18) 45° in an anticlockwise direction until it
releases. Then turn another 45°.
2. If necessary, protect the lock against unintentional actuation with a cable lock
for shut-off valves (material number: 7472D02758) or a lock. The hole diame-
ter is 5 mm.
To unlock the shutoff module:
1. Remove the cable lock for shut-off valves or the lock.
2. Turn the lock 45° in a clockwise direction, then push the lock in up to the end
stop and turn it another 45° in a clockwise direction up to the stop.
Fig. 13: Manually operated shutoff module
18
Lock
7.3.2 Pneumatically and electrically operated shutoff module
To release the operating line:
AVENTICS™ | R422003121-BAL-001-AE | English
15
14
12/13
16
17
17/18
16
18
13
Pressure gauge connection for con-
nection 4
15
Manometer
17
Adjustment screw for connection 2
18
Apply at least the minimum pressure P2, which corresponds with the pressure
u
on connections 2 or 4, to the pilot control connection to actuate the shutoff
module.
6
5
4
3
2
16
1
0
0
1
Fig. 14: Working pressure diagram for pneumatically operated shutoff module
Fig. 15: Pneumatically operated shutoff module
19
Sensor connection M8x1
Fig. 16: Electrically operated shutoff module
30
Electronic pilot valve connection
M8x1
Pneumatically and electrically operated shutoff modules feature posi-
tion detection. A sensor with M8x1 connection can be used to query
the position.
Table 3: Sensor data
Electrical data for the sensor
Behavior
Output
Max. current consumption
Min./max. voltage range
Short-circuit proof
Voltage drop
Protection class according to EN 60529/
IEC 529
Table 4: Pin assignment for sensor connection
4
1
3
2
3
4
5
6
7
Working pressure [bar]
19
20
20
Pilot control connection X Ø 4
30
20
20
Pilot control connection X Ø 4
The sensor signal is supplied when no pilot air
is applied at the shutoff point, i.e. no air flows
through the operating line.
PNP
15 mA
10 ... 30 V
yes
< 2.5 V
IP67 for assembled connection
Pin
Assignment
1
0 V
4
Output
3
+Vs
8
9
10
17