Panel Mounting Flange - WIKA DELTA-comb DPGS40TA Manual De Instrucciones

Ocultar thumbs Ver también para DELTA-comb DPGS40TA:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

7. Options and accessories
Specifications for handling
Sequence of operations to start measurement
1. Open the pressure compensating valve (middle valve spindle)
2. Open the shut-off valve for the negative media chamber (⊖, right-hand valve)
and the positive media chamber (⊕, left-hand valve)
3. Close the pressure compensating valve
Sequence of operations to flush/vent the measuring lines
1. Start: Open the shut-off valve for the ⊕ and ⊖ media chamber, open the
pressure compensating valve and vent valve
2. Finish: Close the pressure compensating valve and vent valve
Sequence of operations to finish measurement (also temporary shutdown)
1. Open the pressure compensating valve
2. Close the shut-off valve for the ⊕ and ⊖ media chamber
Sequence of operations to dismount the measuring instrument with a running
process
1. Close the shut-off valve for the ⊕ and ⊖ media chamber
2. Open the vent valve

7.2 Panel mounting flange

Panel
WIKA operating instructions DPGS40TA with component testing
EN
27

Publicidad

Tabla de contenido
loading

Tabla de contenido