Technical data
Battery change
If the batteries have run down, the battery symbol appears in the display and the device switches off if necessary. Please change
the batteries immediately to ensure the accuracy of the test values.
Disconnect the test probes from the test circuit before opening the battery compartment!
To change the batteries, open the battery compartment on the main housing. To do this, loosen the screws alternately using a sui-
table screwdriver. Make sure that the polarity is correct when using the new batteries. Carefully close and screw the battery com-
partment back shut.
Without batteries, the device indicates an applied voltage above the ELV value by means of an LED.
At lower temperatures below 5°C, the readiness of the voltage tester may be impaired. Please ensure sufficient power supply by
using suitable batteries which are also specified for the temperature range used!
Batteries do not belong in the household waste. There is also a collection point near you!
Technical data
Display
Nominal voltage range
Current measurement
Rotary field display
Frequency display
Nominal current In
Phase testing pole
Continuity check
Operating temperature
Protection class
Overvoltage category
Test standard
Power supply
18
Backlit LC display / LEDs
1...1000 V AC (TRMS)
1...1500 V DC
0.1...200 A AC/DC, 45...65 Hz
Yes
1...800 Hz ±5% +5 digits
< 3.5 mA
> 100 V AC
0,1...500 k
-15 to +55 °C, at > 85% RH
IP 64
CAT IV 600 V, CAT III 1000 V
EN 61243-3:2014, IEC 61010-1:2010
2x 1.5 V type AAA Micro
®
Testboy
TV 230