Refrigerant piping side
770mm / 30.3" (Suspension bolt)
830mm / 32.7"(Body)
900mm / 35.4"(Ceiling opening)
950mm / 37.4"(Panel)
CAUTION
The unit body should align perfectly with the
hole. Ensure that the unit and the hole are the
same size before moving on.
2.
(A)
Drill 4 holes 5cm (2") deep at the ceiling hook
positions in the internal ceiling. Be sure to hold
the drill at a 90° angle to the ceiling.
(B)
Drill 4 holes 12cm-15.5cm (4.7"-6.1") deep at the
ceiling hook positions in the internal ceiling. Be
sure to hold the drill at a 90° angle to the ceiling.
3. Using a hammer, insert the ceiling hooks into
the pre-drilled holes. Secure the bolt using the
included washers and nuts.
4. Install the four suspension bolts.
Page 24
5. Mount the indoor unit. You will need two
Drain hose side
(A)
NOTE: The bottom of the unit should be
10-18mm(0.4-0.7")(
24mm (0.9")(Compact models) higher than
the ceiling board. Generally, L (indicated in
the following gure) should be half the
length of the suspension bolt or long
enough to prevent the nuts from coming o .
Ceiling board
people to lift and secure it. Insert suspension
bolts into the unit' s hanging holes. Fasten
them using the included washers and nuts.
Super-Slim models
Wall
L
10 - 18mm (0.4-0.7")
or 24mm (0.9")
) or
Main body