2.2 Installing inlet adapters

Fig. 2.b
If installing an inlet extension,
a.
Place the gasket on the face of the header's inlet.
b.
Using 7-8 Nm torque (5-6 ft lb), secure the extension adapter to the
header using the fasteners provided in the kit containing the inlet
adapter that will be secured to the extension.
Place the gasket on the face of the inlet of the header or extension.
Using 7-8 Nm torque (5-6 ft lb), secure the inlet adapter using the
fasteners provided. (Fig.2.b) If the inlet adapter is being attached to
an inlet extension, use the fasteners included in the extension kit to
secure the inlet adapter.
To connect the steam supply to the distributor, see section 4 for further
information.
2.3 Steam inlet connection between
ultimateSAM and valve fl ange
(SAKI******)
Connection kits are available for ultimateSAM between the distributor
steam inlet and the valve fl ange.
These kits vary depending on the distributor steam inlet connection
and valve nominal diameter.
SAKIC
x
Family prefix
Pos.
Meaning
Type of connection
Nominal diameter
Region
The kits are available in AISI 316 stainless steel
x x
0
x
1
2 3
Opt.
Description
64
1 1/2"
84
2"
94
2 1/2"
A
DN 15
B
DN 20
C
DN 25
D
DN 32
E
DN 40
F
DN 50
G
DN 65
U
North America
0
Other
Tab. 2.d
The kit codes specifi ed in Table 2.e comprise:
gasket (1);
fl ange (2);
adapter (6);
pipe (3 , 5);
joint (4);
2
1
1
Code
SAKIC64A00
ultimateSAM valve connection kit (DN15 - 1" 1/2)
SAKIC64B00
ultimateSAM valve connection kit (DN20 - 1" 1/2)
SAKIC64C00
ultimateSAM valve connection kit (DN25 - 1" 1/2)
SAKIC64D00
ultimateSAM valve connection kit (DN32 - 1" 1/2)
SAKIC64E00
ultimateSAM valve connection kit (DN40 - 1" 1/2)
SAKIC64F00
ultimateSAM valve connection kit (DN50 - 1" 1/2)
SAKIC84B00
ultimateSAM valve connection kit (DN20 - 2")
ultimateSAM valve connection kit (DN25 - 2" 1/2)
SAKIC94C00
SAKIC94D00
ultimateSAM valve connection kit (DN32 - 2" 1/2)
SAKIC94E00
ultimateSAM valve connection kit (DN40 - 2" 1/2)
SAKIC94F00
ultimateSAM valve connection kit (DN50 - 2" 1/2)
SAKIC94G00
ultimateSAM valve connection kit (DN65 - 2" 1/2)
The minimum distance to allow for correct connection inside the
AHU is D= 100 mm (3.93 in) (Fig. 2.d)
The pipe x is used to pass through the insulating panel on the AHU.
15
"ultimateSAM - user" +0300070ES - rel. 1.0 - 23.05.2013
4
3
4
3
6
5
2
Fig. 2.c
Description
NOTE
also used with
SA0*
AHU
D
AHU
D
Fig. 2.d
ENG
Tab. 2.e