ELECTRICAL AND CONTROL SETTINGS
Input - All input codes descriptions:
Input codes
Mark
i - 00
No Function
Smart Act./
i - 02
SG Ready Input 1
Swimming pool
i - 03
Demand ON/OFF
i - 04
Solar in
i - 05
Forced Heating/Cooling
i - 06
DHW Boost
i - 07
Power meter 1
i - 08
Demand ON/OFF 1
i - 09
Demand ON/OFF 2
i - 10
Forced heating
i - 11
Forced cooling
i - 12
Power meter 2
i - 13
Cycle 1 and 2 ECO mode
i - 14
Cycle 1 ECO mode
i - 15
Cycle 2 ECO mode
i - 16
Force OFF
i - 17
SG Ready Input 2
-
This function must be used to stop or limit the heat pump and Auxiliary electric heater
when restricted by Electric company. It allows an external Smart switch device to switch
off or reduce consumption of the heat pump and Auxiliary electric heater during time of
peak electricity demand.
In case of using Smart Grid application, this input is used as a digital input 1 and allows
four different operating modes.
Optional input signal can be configured as function of "Swimming pool Demand ON/OFF"
to operate SWP. Switch ON/OFF of SWP can also be controlled by master controller.
Closed: Start SWP operation (Switch ON and Demand ON) Open: Stop SWP operation
(Switch OFF and Demand OFF)
In case of combining Unit with solar panels, this input is used as a feedback for solar
station ready operation.
Closed: Solar in ON to trigger solar pump operation ON
Open: Solar in OFF to trigger solar pump operation OFF
Heating/cooling can be changed by an input of an external contact signal.
Heating/cooling can also be changed over by master controller.
Closed: Heating mode
Open: Cooling mode
With this function enabled, it is possible to request a heating up of the DHW when user
requires an instantaneous delivery of DHW. Triggering input signal can also Switch ON
DHW.
Input used as kW/h pulse count for Energy data recording, used to count energy data or
the total energy data.
Optional input signal can be configured as function of "Demand ON/OFF 1" or "Demand
ON/OFF 2" and selected as room thermostat.
Closed: Corresponding room thermostat Switch ON and Thermo ON.
Open: Corresponding room thermostat Switch OFF and Thermo OFF.
Corresponding room thermostat can also be Switch ON/OFF by Rooms function on
Master controller.
Forced Heating mode by input of contact signal, Heating can also be changed over by
master controller.
Closed: Forced Heating mode
Open: No action
Forced Cooling mode by input of contact signal, Cooling can also be changed over by
master controller.
Closed: Forced Cooling mode
Open : No action
Input used as kW/h pulse count for Energy data recording, used to count energy data or
the total energy data.
Cycle 1 and Cycle 2 Water ECO offset. Current water temperature setting is reduced or
increased by the indicated parameter in space heating mode or space cooling mode.
Closed: Cycle 1 and Cycle 2 Water ECO offset enabled
Open: Cycle 1 and Cycle 2 Water ECO offset disabled
Cycle 1 Water ECO offset. Current water temperature setting is reduced or increased by
the indicated parameter in space heating mode or space cooling mode.
Closed: Cycle 1 Water ECO offset enabled
Open: Cycle 1 Water ECO offset disabled
Cycle 2 Water ECO offset. Current water temperature setting is reduced or increased by
the indicated parameter in space heating mode or space cooling mode.
Closed: Cycle 2 Water ECO offset enabled
Open: Cycle 2 Water ECO offset disabled
Force OFF the unit include Water Cycle 1, Water Cycle 2, DHW and SWP. Switch ON/
OFF of different function can also be controlled by master controller.
Closed: Forced OFF the unit include Water Cycle 1, Water Cycle 2, DHW and SWP.
Open: No action
In case of using Smart Grid application, this input is used as a digital input 2 and allows
four different operating modes.
30
Description