Cable section in mm²
10 m
20 m
30 m
4 A
1,5
1,5
1,5
8 A
1,5
1,5
1,5
12 A
1,5
1,5
2,5
16 A
2,5
2,5
2,5
20 A
2,5
2,5
4
24 A
4
4
4
28 A
6
6
6
32 A
6
6
6
36 A
10
10
10
40 A
10
10
10
44 A
10
10
10
48 A
10
10
10
52 A
16
16
16
56 A
16
16
16
60 A
16
16
16
Table valid for 4-core PVC cables (3 phases + earth) @ 400V.
Table 2: Cable section
5.4
Connection of the Differential Pressure Sensor
The MCE-150/C accepts two types of differential pressure sensor: ratiometric with full scale value 4 bar or
ratiometric with full scale value 10 bar.
The cable must be connected at one end to the sensor and at the other to the pressure sensor input
provided on the inverter, marked "Press 1" (see Figure 3).
The cable has two different ends with obligatory direction of connection: connector for industrial applications
(DIN 43650) on the sensor side and 4-pole connector on the MCE-150/C side.
ENGLISH
40 m
50 m
60 m
70 m
1,5
1,5
1,5
1,5
1,5
2,5
2,5
2,5
2,5
4
4
4
4
4
6
6
4
6
6
10
6
6
10
10
6
10
10
10
6
10
10
10
10
10
10
16
10
10
16
16
10
10
16
16
10
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
Figure 3: Connections
80 m
90 m
100 m
1,5
2,5
2,5
4
4
4
6
6
6
6
10
10
10
10
10
10
10
16
10
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
40
120 m
140 m
160 m
180 m
2,5
2,5
4
4
6
6
6
10
10
10
10
10
10
10
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
16
200 m
4
10
16
16
16
16
16
16
16
16
16
16
16
16
16