Type RPC D/PID positioner
5.7
Bus status display
The bus status is indicated via the display on the device.
Display indication
Device state
(is displayed every 3
seconds)
BUS no connection
Online, no connection to
the Master
BUS critical err
Critical bus error
5.8
BUS.COMM – Settings on the type RPC
Set the following menu items in the BUS.COMM menu for putting into operation the EtherNet variant:
Command
BUS FAIL
SafePos
SAFEPOS
30
Explanation
Device is properly connected to the bus, the
network access procedure was completed
without errors. However, there is no established
connection to the Master.
Other device with the same address in the
network. BUS offline as a result of communica-
tion problems.
Explanation
Activate or deactivate approach to safety position
off
The actuator stops in the position corresponding to the last transmitted setpoint value
(default setting).
on
The behavior of the actuator in the event of an error in bus communication depends on the
activation of the additional SAFEPOS function.
See operating instructions in chapter "SAFEPOS – Entering the safety position".
energized
The actuator moves to the safety position specified in the SAFEPOS additional function.
de-energized
The actuator moves to the safety end position which it would assume in the event of failure of the
electrical and pneumatic auxiliary power.
See operating instructions in chapter "Safety end positions after failure of the electrical or
pneumatic auxiliary power"
Operating Instructions
Troubleshooting
New connection establish-
ment by Master
Change the address of
the device and restart the
device.
Error analysis in the net-
work with a bus monitor.