Installation
English
Installation of drain pipes
1. Drainage pipes must have good insulation measures. Specific measures are as follows
a: Drainage pipes must be securely fastened with the inner water outlet and drain pipe respectively and
secured with a washer, as shown in Fig. 1.
b: Wrap the thermal insulation cotton in the drain insulation tube and washer, as shown in Fig. 2.
c: Tighten the sponge with a bandage, as shown in Fig 3-.
2. The drain pipe should have a downward slope (1/50~1/100).
If the drain pipe is installed up and down or upwards, it will result in water backflow or leakage, etc.
3. During pipe connection, do not apply too much force to the drainage joint of the indoor unit.
4. There is a drain hole on each side of the indoor unit; the unused drain pipe should be closed.
be closed.
Note: The drain pipe must be wrapped in thermal insulation material, otherwise it will cause condensa-
tion or water droplets.
Thermal insulation material: rubber insulation tube thicker than 8mm.